Specifications
B
IPMI Commands and Managed Sensors
136
25h +1.1V Minor voltage high Voltage over 1.17V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 1.23V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 1.29V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 1.05V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 0.99V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
26h +1.1V_VTT Minor voltage high Voltage over 1.28V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 1.34V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 1.37V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 0.96V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 0.90V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
27h +1.0V_BASE Minor voltage high Voltage over 1.05V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 1.10V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 1.15V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 0.95V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 0.90V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
Table 38. Sensor alarms and recommended actions (sheet 12 of 14)
Number Name Alarm level Possible errors or faults Recommendation