Specifications
B
IPMI Commands and Managed Sensors
132
19h +12V Minor voltage high Voltage over 12.6V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 13.2V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 13.8V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 11.4V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 10.8V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
1Ah +5V Minor voltage high Voltage over 5.25V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 5.49V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 5.75V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 4.76V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 4.5V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
1Bh +5V_Standby Minor voltage high Voltage over 5.25V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 5.5V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 5.75V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 4.75V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 4.5V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
Table 38. Sensor alarms and recommended actions (sheet 8 of 14)
Number Name Alarm level Possible errors or faults Recommendation