User manual
Chapter 5
Commands
5-2
The command: Has the
value of:
Configures the PLC-5/VME processor to
copy a block of data:
Continuous copy to VME 0001 from its data table during each ladder scan.
Continuous copy from VME 0002 into its data table during each ladder scan.
See Appendix A for a sample implementation of this command.
You can only enable these operations when the PLC-5/VME processor is in
Run mode. You can specify up to 1000 words as the transfer length.
These words must be contiguous elements in files, but the transfer can span
files (Figure 5.1).
Figure 5.1
Continuous-Copy
Command Structure
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0Word
Command word
Response word
Cmd interrupt level
Command interrupt status/ID
Reserved
0
1
2
3
4
15
Reserved
Reserved
Reserved
Reserved
WidthEnable Address modifier
Data address (high)
Data address (low)
Data size
Data table file number
Element number
Reserved
Reserved
Op interrupt level
Op status/ID
Reserved
5
6
7
8
9
10
11
12
13
14
Continuous-Copy
Commands