Installation guide
D9412G/D7412G Operation & Installation Guide
43488D Page 44 © 2002 Radionics
D9412G/D7412G
Off-board Points
The sixth column shows the
Debounce Count for the point. See
Debounce Count
in the
D9412G/
D7412G Program Entry Guide
.
The seventh column shows the
BFSK report code. It is the point
number reported for this point when
the panel is using the BFSK format.
The eighth column contains the text
displayed at command centers for
the point. The text is transmitted to
the receiver when the panel is using
the Modem IIIa
2
format.
POPIT Labels
Off-board points for the D9412G are
numbered 9 to 127 and 129 to 247
(D7412G uses Points 9-75 only).
The D9412G reserves Points 128
and 248 for internal use. POPITs
must be connected for Points 129 to
247 to expansion loops connected to
POPEX #2.
Two sheets of peel-off POPIT labels are supplied with the D8125 POPEX Module. Use the sheet marked
Bank1
for Points 9 to 127. Use the sheet marked
Bank2
for Points 129 to 247.
Each label has two parts. Place the smaller part, with just the point number on it, on the chip. Place the larger part
with the switch settings on the base of the POPIT. Set the switches and cover the POPIT.
Do not program two POPITs for the same point number. After programming all the points, perform a service walk
test. The
D9412G/D7412G Installation and Troubleshooting Quick Reference Guide
contains instructions for
performing a service walk test. If a point does not test, check the programming for a duplicated address.
Walk test does not show extra points:
Only the Service Walk Test shows extra points. If the point assignment
switches on a POPIT or OctoPOPIT are set incorrectly, it may create both missing and extra points. If the same
point number is assigned to two or more POPITs or OctoPOPITs, none of the points with that number will test
correctly.
8.4 D8128D OctoPOPIT Module
D8128, D8128A or D8128B modules are not compatible with the D9412G or D7412G. Only use the D8128D
OctoPOPIT module. Using D8128, D8128A or D8128B modules may cause intermittent missing and
restoral reports.
8.4.1 Description
The D8128D OctoPOPIT Module combines the functions of the D8125 POPEX module and the D8127/D9127
POPIT modules to provide eight off-board points in a single module. You can wire both D8128D OctoPOPIT and
D8125 POPEX modules in parallel to the ZONEX Bus terminals on the same panel.
Review section
5.0 Power Outputs
to be sure to provide enough power for the OctoPOPITs and other powered
devices that will be connected to the system.
8.4.2 Listing
The D8128D OctoPOPIT Module is UL listed for Local or Police Connected Burglary Alarm, Central Station Burglary
Alarm, and Household Burglary Alarm applications. The D8128D is also suitable for fire supervisory applications,
such as indicating circuit supervision (using the D192C Bell Circuit Supervision Module), sprinkler supervision,
and valve tamper protection.
Do not connect fire alarm initiating devices directly to the D8128D.
You must use the D125B Dual Class B Powered Loop Interface Module or D129 Dual Class A Initiation Circuit
Module for fire initiation applications. Connect the initiating devices, smoke detectors for example, to the D125B
powered loops or D129 Class A loops.
D9412G/D7412G
Default values are shown in ( ) or in
bold
RADXPNTS Handler
Point Assignments (001 through 040)
POPIT Switch
Setting
Trans-
lation
Point
#
Point
Index
Area
Assign
Debounce
BFSK/
Relay
Custom Point Text
100 001 __ __ (1) ____ (2) _____ (1) ____
P1 FIRE
___________________
200 002 __ __ (1) ____ (2) _____ (2) ____ P2 PANIC ___________________
300 003 __ __ (1) ____ (2) _____ (3) ____ P3 DELAY ___________________
400 004 __ __ (1) ____ (2) _____ (4) ____ P4 FOLLOW ___________________
500 005 __ __ (1) ____ (2) _____ (5) ____ P5 INSTANT ___________________
600 006 __ __ (1) ____ (2) _____ (6) ____ P6 INSTANT ___________________
700 007 __ __ (1) ____ (2) _____ (7) ____ P7 INSTANT ___________________
800 008 __ __ (1) ____ (2) _____ (8) ____ P8 INSTANT ___________________
0 1 2 3 4 5 6 101 009 __ __ (1) ____ (2) _____ (1) ____ P9 ___________________
0 1 2 3 4 5 _ 102 010 __ __ (1) ____ (2) _____ (1) ____ P10 ___________________
0 1 2 3 4 _ 6 103 011 __ __ (1) ____ (2) _____ (1) ____ P11 ___________________
0 1 2 3 4 _ _ 104 012 __ __ (1) ____ (2) _____ (1) ____ P12 ___________________
0 1 2 3 _ 5 6 105 013 __ __ (1) ____ (2) _____ (1) ____ P13 ___________________
0 1 2 3 _ 5 _ 106 014 __ __ (1) ____ (2) _____ (1) ____ P14 ___________________
0 1 2 3 _ _ 6 107 015 __ __ (1) ____ (2) _____ (1) ____ P15 ___________________
0 1 2 3 _ _ _ 108 016 __ __ (1) ____ (2) _____ (1) ____ P16 ___________________
0 1 2 _ 4 5 6 109 017 __ __ (1) ____ (2) _____ (1) ____ P17 ___________________
0 1 2 _ 4 5 _ 110 018 __ __ (1) ____ (2) _____ (1) ____ P18 ___________________
0 1 2 _ 4 _ 6 111 019 __ __ (1) ____ (2) _____ (1) ____ P19 ___________________
0 1 2 _ 4 _ _ 112 020 __ __ (1) ____ (2) _____ (1) ____ P20 ___________________
0 1 2 _ _ 5 6 113 021 __ __ (1) ____ (2) _____ (1) ____ P21 ___________________
Figure 15: Program Record Sheet