Installation guide

D9412G/D7412G Operation & Installation Guide
43488D Page 28 © 2002 Radionics
D9412G/D7412G
4.2.6 Battery Discharge/Recharge Schedule
Discharge Cycle
AC OFF AC fail report when AC fails if panel is
programmed to report AC failure at
occurrence.
13.9 VDC Charging float level
13.8 VDC Charging Status LED on
12.1 VDC Low Battery & AC fail reports if
programmed; Low Battery LED on
10.2 VDC Battery load shed (processing
functions continue if AC is
present)
Recharge Cycle
AC ON Load shed relay resets, battery
charging begins, battery trouble
and AC restoral reports sent.
13.7 VDC Battery restoral reports sent, Low
Battery LED off
13.9 VDC Charging Status LED off, battery
float charged
4.3 Charging Status and Low Battery LEDs
Table 7: Charging Status and Low Battery LEDs
LEDs Off When Normal
Char
g
in
g
Status
Low Batter
y
YEL
RED
Figure 6: Charging and Battery LEDs
Power Supply
Type LED
Color
LED
State
Action
Yellow Shows the charging status of the battery.
Figure 6
shows its location.
Yellow Off Battery is fully charged.
If the battery is missing, shorted, or reversed: The Charging Status
LED is off, but the red Low Battery LED is flashing.
Yellow On
Battery float charge is below 13.8 VDC. If AC is present the battery is
charging.
When the combined current draw from all outputs exceeds 1.4 amps.
This is normal under alarm conditions for non-fire systems with sirens or
bells draw more than 1.4 amps. If the LED comes on regularly for
extended periods or doesn’t go out, check the current draw for devices
connected to the power outputs. See section 5.0
Power Outputs
for
instructions.
Yellow
Flash
once/min
System is checking the battery.
Charging
Status
LED
Yellow
and Red
Flash
once/min
When the current draw for devices connected to the power outputs
exceeds 1.4 amps and/or the battery is missing.
Red Shows the condition of the battery.
Figure 6
shows its location.
Red Off When the battery is fully charged.
Red On Battery voltage as fallen below 12.1 VDC. LED goes out when voltage
reaches 13.7 VDC.
Red
Flash
(same
rate as
Green
LED)
Green LED is Operation Monitor LED.
Battery is missing or shorted.
Low
Battery
LED
Red and
Yellow
Flash
once/min
When current draw for devices connected to the power outputs exceeds
1.4 amps and/or the battery is missing.