Installation guide

D6600 NetCom
C900TTL-X Configuration
D6600 NetCom System Guide
46542C Page 74 © 2001 Radionics
Table 20 identifies the Dialer Format settings possible for switch positions 1 through 4 (the switch positions will
be referred to as DS-1 for Dipswitch 1, etc):
DS-1 DS-2 DS-3 DS-4 Dialer Format of Host Alarm Panel
OFF OFF OFF OFF Radionics MODEM IIe and MODEM IIIa
2
(D7212, D9112 & equivalent)
OFF OFF OFF ON Radionics MODEM II (D4112, D6112, D7112, D8112 and equivalent)
OFF OFF ON OFF Any ADEMCO DTMF format (4+2 EXPRESS, ADEMCO High Speed, Contact
ID)
OFF OFF ON ON Any ADEMCO DTMF where the dialer retransmits quickly
OFF ON OFF OFF 2300 Hz ACK Tone, RADIONICS BFSK
OFF ON OFF ON 1400 Hz ACK Tone, RADIONICS BFSK
OFF ON ON OFF Reserved
OFF ON ON ON Reserved
ON OFF OFF OFF 2300 Hz ACK Tone, Any digital pulse type format
ON OFF OFF ON 1400 Hz ACK Tone, Any digital pulse type format
ON OFF ON OFF Long 2300 Hz ACK Tone, Any digital pulse type format
ON OFF ON ON Long 1400 Hz ACK Tone, Any digital pulse type format
ON ON OFF OFF Unused
ON ON OFF ON Unused
ON ON ON OFF Unused
ON ON ON ON Unused
Table 20: C900TTL-X Dialer Format Settings – Dipswitches 1 - 4
Dipswitch positions 5 through 10 (Table 21) set up the C900TTL behavior, based upon the application. See the
notes below the table for more information. (The switch positions will be referred to as DS-5 for Dipswitch 5, etc):
Switch and Condition APPLICATION
DS-5 ON Enable AUTO FALLBACK condition after detection of an intercept error
DS-5 OFF Disable AUTO FALLBACK condition after detection of an intercept error
DS-6 ON No number of hang-ups will cause FALLBACK MODE
DS-6 OFF Third hang-up without D6600 or host computer ACK causes error.
DS-7 ON Default 240 second poll of D6600 or host computer during idle state
DS-7 OFF Default 30 second poll of D6600 or host computer during idle state
DS-8 ON C900 will send initial handshake to Alarm Panel after 6 second break in dialing
DS-8 OFF C900 will send initial handshake to Alarm Panel after 1 second break in dialing
DS-9 ON Unused
DS-9 OFF Unused
DS-10 ON 9600 BAUD data rate from C900 to onboard Network interface
DS-10 OFF 1200 BAUD data rate from C900 to onboard Network interface
Table 21: C900TTL-X Dipswitches 5 – 10
Note: Several errors can occur in the intercept process. Any error will force the C900TTL-X to switch the Alarm Panel
dialer to the Fallback (phone line backup) position for 2 minutes when the Alarm Panel next seizes the line (if
enabled, and if the seize occurs within 2 minutes). Intercept errors are always reported to the D6600 Receiver. If
the D6600 Receiver does not acknowledge a signal sent that was intercepted by the C900TTL-X in the proper
amount of time, the Alarm Panel digital dialer will hang up and retry the message transmission.