6.0 RAM IV NetCom Programming
6.1 RAM IV And D5200 Programmer Handler Requirements
In order to program the D6600 NetCom parameters for the 9000 Series panels, you must use RAM IV version
2.9 or higher and a new handler called RADXAUX1. To add the RADXAUX1 handler to your D5200 Programmer,
call the Radionics Handler Update System at (831) 757-1190.
For further information on programming 9000 Series panels, please refer to the 9000 Series Program Entry
Guide (P/N: 74-07695-000) and the RAM IV Operation Manual (P/N: 38849).
This handler currently has six sections: SDI Automation, SDI RAM Parameters, Enhanced Communications,
Route Group Attempts, SDI RAM/Enhanced Communication Configuration, and Miscellaneous. The D5200
handler required for these options is found in the RADXAUX1 handler, version 1.2 and is available on the
Handler Update System at Radionics. Each of the sections within RADXAUX1 are listed in order below:
6.1.1 SDI Automation
This section allows you to define the characteristics of the D9133 Serial Interface Module when used with Home
or Business Automation software. The D9133 Serial Interface Module is a bi-directional SDI to RS232 interface
module that allows the 9000 Series panels, version 6.00 and higher, to send/receive information to/from an
external software program. This Automation protocol will allow external software programs perform functions
such as arming and disarming areas, changing user passcodes and names, and turning relays on and off to
name a few. The following items allow some simple configuration options, however, to receive the D9133
Automation protocol you must contact Radionics’ Marketing Department in Salinas, CA at 800-757-8877.
Enable SDI Auto
Default: No
Selections: Yes or No
Turning this item to Yes enables the automation address for use with PC9000 software (SDI Address 80).
Yes Enable PC9000 Automation software.
No Disable PC9000 Automation software.
Baud Rate
Default: 9600
Selections: 300, 1200, 2400, 4800, 9600, 14.4K
This item determines the baud rate between the D9133 and the external hardware connected to it. Since the SDI
bus communicates at 9600 baud, Radionics recommends that this prompt also be kept at 9600 baud. Pressing
the [SPACE] bar on the D5200 toggles through the available options.
Parity / Stop
Default: No / 1
Selections: No / 1, No / 2, Odd / 1, Even / 1
This prompt addresses two items; Parity and the number of Stop Bits. Pressing the [SPACE] bar on the D5200
toggles through the available options.
No / 1
THIS IS THE SETTING NECESSARY FOR NetCom NETWORK COMMUNICATIONS
No / 2 No Parity, 2 Stop Bits
Odd / 1 Odd Parity, 1 Stop Bit
Even / 1 Even Parity, 1 Stop Bit