12. Troubleshooting
12.1 Introduction
Use this guide to help troubleshoot problems with the
D9124 Control Panel. To prevent problems from
occurring, read the preceding sections and the D9412G /
D7412G Program Entry Guide to verify the control panel
is correctly installed and programmed.
12.2 Self-Diagnostic Tests
D9124 Control Panel performs a series of self-diagnostic
tests of hardware, software, and programming at start up
and reset.
12. Troubleshooting
Buzzer sounding is normal at start-up: The on-board
buzzer, located on the lower right corner of the control
panel, sounds as the D9124 performs self-diagnostic tests
at start up and reset. These tests take less than 2 seconds.
If all tests complete successfully, the buzzer turns off.
The control panel continues periodic internal testing
during normal operation. If a fault is detected during
testing, the buzzer sounds.
Table 16 identifies system problems that display during
self-diagnostic tests and describes how to troubleshoot
them.
Table 16: Self-Diagnostic Tests
Problem Diagnosis Solution
CALL FOR SERVICE
appears in
the command center display. No
buzzer sounds at the command
center.
A command center stopped receiving
data from the control panel.
Check the wiring for opens, grounds, or shorts.
COMM FAIL ROUTE #
appears in
command center displays.
The control panel made ten
unsuccessful attempts to report to the
receiver.
See
Section 12.6 Communication Failure
.
Press [ESC] to silences the buzzer. The
display clears when communication restores
(such as the receiver acknowledging a
report).
PANEL BROKEN
appears in the
displays of all command centers,
the command center buzzer sounds,
and the green Operation Monitor
LED stops flashing or is off.
A hardware or software problem
occurred.
Pressing [ESC] does not silence the buzzer.
Return the control panel to Bosch Security
Systems for repair. See
Section 3. Installation
for
information on installing a working control panel.
PARAM FAIL
alternates with the
idle text at the command centers,
the command center buzzer sounds,
the green Operation Monitor LED
continues flashing, and the control
panel sends a Bad Param Cksum
Report to the receiver.
The program is corrupted.
Pressing [ESC] might silence the buzzer.
Silencing the buzzer does not correct the
problem.
The corrupted copy of the program in
the control panel must be replaced. Load a new
copy of the complete program. The displays clear
when the control panel is reset after loading a
new program. See
Section 10. Programming
.
SERVC AC FAIL
appears in the
command center displays.
AC power was interrupted at
Terminals 1 and 2.
Press [ESC] to silence the buzzer. Restoring
power clears the display.
Note: Program the control panel to send an AC
Fail Report to the receiver.
SERVC BATT LOW
appears in the
command center displays.
Battery voltage at Terminals 4 and 5
fell below 12.1 VDC.
See
Section 12.11 Battery and Power
Reports
for probable causes and remedies.
Press [ESC] to silence the buzzer. The
display clears when battery voltage reaches
13.7 VDC.
SERVC BATT MSING
appears in
the command center displays.
The control panel cannot detect a
battery at Terminals 4 and 5.
Press [ESC] to silence the buzzer. Restoring the
battery clears the display.
Note: Program the control panel can to send a
Battery Missing Report to the receiver.