Installation guide

Bosch Security Systems | 11/03 | 39352E
EN | 44
D9124 | Operation & Installation Guide |
5. Enter a passcode assigned an authority level with
access to the Service Walk Test function. Then press
[ENT].
6. When 246 PTS TO TEST appears, test the first
detection device.
As you fault the detection devices, the command
center emits a short tone, briefly displays the point
text for the point tested, and returns to the points to
test display.
Extra Points display default text. If you
incorrectly set the addresses on a POPIT to
a point number that is not in your control
panel program, the default text for that point
number (
POINT ###)
displays when you
fault the point. The
D9124 Program Record
Sheet
shows the default text for all points.
Faulting the point a second time produces the tone
and displays the point text, but does not reduce the
Pts to Test count.
7. During the Service Walk Test, view the points that
remain untested by pressing [ESC] when point text
appears.
11. Testing the System
8. When the display shows ### PTS TO TEST, press
[ESC].
9. VIEW UNTESTED ? appears. Press [ENT].
10. When ### PTS UNTESTED appears, press
[NEXT] to see a list of the points that were not yet
tested. Continue pressing [NEXT] to scroll through
this list.
11. To resume the Service Walk Test, press [ESC].
12. When the display shows ### PTS UNTESTED,
press [ESC].
13. ### PTS TO TEST appears and you can resume
testing points.
14. Press [ESC] twice to end the Service Walk Test.
After testing the last point, the display shows 0 PTS
TO TEST. Press[ ESC]. The display momentarily
shows ALL PTS TESTED before returning to idle
text.
Automatic time-out returns the system to idle text. If
there is no point or command center activity for
20 minutes, the Walk Test ends automatically and the
D9124 System sends a restoral message to the receiver.
The command center returns to idle text.