11. Testing the System
11.1 Fire Test
Test fire points to confirm they function properly. You
can review untested points at the command center to
help pinpoint any problems.
Upon initiation, the Fire Test tests the fire alarm output
and activates the command center fire sounder for 2
seconds. The AC disables for 4 minutes to test the
system’s battery power. If the battery cannot maintain
the system for the 4-minute period, the command center
appears to go dead. At the end of the 4-minute period,
AC returns to the system and the control panel restores.
A message is sent to the receiver upon initiation and
completion of the Fire Test.
During the Fire Test, no alarms are sent to the central
station.
If there is no activity on the system for 20 minutes, the
system automatically exits from the Fire Test and sends a
restoral message to the receiver.
11.1.1 Using Fire Test
1. Press [ESC] on the D1256 Command Center to
enter the menu.
2. Press [NEXT] repeatedly until you reach the FIRE
TEST ? prompt and then press [ENT].
The display shows ### PTS TO TEST.
3. Activate the detection devices one at a time to fault
each point.
As you activate each point, your command center
shows the point text for 60 seconds and rings the fire
sounders for 2 seconds. This verifies the detection
device is working properly. The D9124 System
automatically resets smoke detectors.
When a resettable point (such as a smoke detector) is
faulted, the display shows SENSOR RESETTING for
5 seconds. During this time power is removed from
smoke power relays.
Activating a point more than once does not
increment the test count. The command center emits
a brief tone and displays the point text each time
you fault the point allowing you to test multiple
devices assigned to one point.
4. When all 24-hour points are tested, 0 PTS TO
TEST appears. Press [ESC]. The display
momentarily shows ALL PTS TESTED before
returning to idle text.
5. During the Fire Test you can see the points that
remain untested. When point text appears, press
[ESC].
6. When the display shows
### PTS TO TEST press
[ESC].
7. VIEW UNTESTED ?
appears. Press [ENT].
8. The display shows ### PTS UNTESTED. Press
[NEXT] to see a list of the points that are not yet
tested. Continue pressing [NEXT] to scroll through
the list.
9. Press [ESC] to resume the Fire Test. ### PTS
UNTESTED
appears.
10. Press [ESC]. The display shows ### PTS TO
TEST and you can resume testing points.
11. Press [ESC] twice to end the Fire Test.
Automatic time-out returns the system to idle
text. If there is no point or command center
activity for 20 minutes, the Fire Test ends
automatically and the D9124 System sends
a restoral message to the receiver. The
command center returns to idle text.
11.2 Service Walk Test
The Service Walk Test differs from the standard Walk
Test. POPITs whose addresses are set for a point
number not programmed in the control panel appear in
the Service Walk Test.
The Service Walk Test is only available at
command centers with a panel-wide scope.
Refer to the
Command Center
sections in
the
D9412G/D7412G Program Entry Guide
for a description of command center scope.
Fire and other 24-hour points do not transmit
reports to the receiver during the Service
Walk Test.
To perform a Service Walk Test:
1. Choose a command center with panel-wide scope to
conduct the test. Be certain the display shows the
idle disarmed text.
2. Press [MENU] to enter the Function List, or press
[9] [9] [ENT] to show the first item in the Service
Menu.
3. Press [NEXT] to step through the menu items until
SERVICE WALK?
appears in the display.
4. Press [ENT]. If you programmed Service Walk Test
access to be restricted by authority level, ENTER
PASSCODE appears in the display.
11. Testing the System