Installation guide
Bosch Security Systems | 11/03 | 39352E
EN | 26
D9124 | Operation & Installation Guide |
6. ZONEX, Addressable Points
Table 9: D8125 Wiring
Wire Color D8125 Terminal
Gray - TB2 - 2
Violet + TB2 - 3
Black GND TB1 - 1
Orange OUT TB1 – 2
Green IN TB1 – 3
Red AUX TB1 – 4
Figure 14: Connecting Field Wiring to Motherboard
S
SS S
PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL PL
SSSSSS S S SSS SSS S S
+ - + - + - + - + - + - + - + -
8654321 7
*
*
**
*
*
PL
PL
1 2 3 4 5 6 7 8 9 1011 1213141516171819 202122232425 26
1
2
3
4
5
6
8
7
9
11
10
13
12
1 - D8125 POPEX #1 data loops 8 - Smoke detector power (-)
2 - D8125 POPEX #2 data loops (optional) 9 - D1255, D1256, D1257 (or other fire annunciators)
3 - Red 10 - 560
Ω
, 2W EOL resistor (P/N: 15-03130-005)
4 - Black 11 - Style W circuit
5 - Yellow 12 - POPIT loops (maximum number = 238)
6 - Green 13 - Style 3.5 circuit
7 - Smoke detector power (+)