User's Manual

MC-Series Standard Capacity system
998-1019-01 Rev X1
8-2 ©2008 RadioFrame Networks, Inc. MC-Series
Proprietary and Confidential Information
8.1 Maintenance
A report of the MCSC system should be maintained and left on site. This report will
provide metrics for possible concerns with individual components and/or the entire
system. It is important that the technician performing the checks understand the
equipment theory and operation. Review the documentation (references) prior to
verification and performing service.
For non-RadioFrame Networks hardware, refer to the equipment manufacturer’s
documentation for maintenance information and procedures. For the iSCIII and the
EAS, refer to the Gen 3 Site Controller System Manual, Motorola, 68P80801E30-O.
For the CSU, refer to the manufacturer's documentation for preventive maintenance
information.
8.1.1 Annual Maintenance
Conduct the following annual maintenance:
Visually inspect all equipment in the MCSC system cabinet for loose or
foreign items and for visible damage.
Verify site-configuration cabling is correct.
Conduct the BER test on each RadioBlade transceiver. Refer to Appendix E
(BER Test Procedure).
Conduct the TOR Tx measurement (RF output measurement) on each
transmitter.
8.2 Troubleshooting Guidelines
Technicians should conduct the following troubleshooting steps in order:
1. Visually inspect for fault indication (LEDs).
2. Inspect the Alarm Manager, and follow alarm resolution procedures. Refer to
the Alarm and Event Guide as well as sections 8.4 (Software Alerts) and 8.5
(RadioBlade Transceiver Alarm Handling) of this Implementation Guide.
3. Contact the RadioFrame Networks Technical Assistance Center at: (800) 328-
0847. Also, refer to section Appendix G (Repair and Technical Support).
4. Copy and save the serial log upload if directed; refer to section 8.7 (Serial Log
Upload Procedure).
5. Refer to sections 9.2 (Power Down Procedure) and 9.1 (Field Replaceable
Units (FRUs)) as necessary.