Installation Guide
Table Of Contents
- Title
- Contents
- Introduction
- System Description
- Pre-Installation
- Receipt of Equipment
- Site Planning
- Main Rack and Supporting Hardware
- Remote ACUs
- RFUs
- RadioBlades
- RAPs
- URU
- Interconnecting Cabling
- Main Rack Configuration
- RF Planning
- Site Survey
- Alarm Configuration
- Tools Required
- Installation
- Equipment Commissioning
- iDEN Interface
- Power Plant
- RadioFrame System
- Coverage Validation
- Site Acceptance Guidelines
- RadioFrame System Functionality Test
- RadioFrame System iDEN Functionality Test
- Interconnect & Dispatch Setup & Voice Quality
- Packet Data Service Connection and Latency
- Short Message Service
- Handover and Cell Reselection
- Interconnect Connection Stability and SQE Performance
- Dispatch Connection Stability
- Idle SQE Testing and Validation
- System Self-Recovery Test
- Packet Data Stability and Throughput
- Validation of ‘Unable to Key BR’ Alarm
- Rectifier & AC Power Alarms
- iSC-3 Functionality Test
- RadioFrame System iDEN Functionality Test
- Connecting the RFS to the Customer LAN
- Operations and Maintenance
- Appendixes
RadioFrame System
Pre-Installation
RFN_3.1 Beta 37
Operating Ambient Temperature
iDEN Interface iSC-3 -40ºF to +185ºF
(-40ºC to +85ºC)
-22ºF (-30ºC) +140ºF (+60ºC)
EAS -40ºF to +185ºF
(-40ºC to +85ºC)
+32ºF (0ºC) +122ºF (+50ºC)
CSU -40ºF to +185ºF
(-40ºC to +85ºC)
+32ºF (0ºC) +122ºF (+50ºC)
Power Plant Rectifier -40ºF to +185ºF
(-40ºC to +85ºC)
+32ºF (0ºC)
Sea level to
4800’: 122ºF
(50ºC)
4800-7000’:
113ºF (45ºC)
7000-10,000’
+104ºF (+40ºC)
Battery 77ºF (+25ºC) -40ºF (-40ºC) +122ºF (+50ºC)
* Altitude: -200 to +8,000 feet above mean sea level; above 8000’ reduce maximum operating ambient
temperature by 2ºC per 1000’ to a maximum of 13,000’.
System Unit Relative Humidity
RadioFrame System NCU 10-90% non condensing
ACU 10-90% non condensing
iDEN Interface iSC-3 5-90% non condensing
EAS 5-90% non condensing, non-operating
0-90% non-condensing, operating
CSU 5-90% non condensing
Power Plant Rectifier 5-90% non condensing
Battery N/A
3.3.7 Heat Load
System Unit BTUs per Hour
RadioFrame System NCU 700
ACU 700
iDEN Interface iSC-3 (1) 140
iSC-3 (2) 140
EAS 170
CSU 17
Power Plant Rectifier 13.5 KBTUs (max)
Battery 683