Conduct an onsite walk through to verify that the following Site Development
Punch List items have been properly installed. This inspection ensures that the
site installation meets quality standards.
Grounding
- buss bar OK (optional)
- NCU/ACU rack(s)
- rectifier rack
- battery shelf (GNB)
Peco II Rectifier Voltages (measured voltages)
- float voltage
- equalize voltage
- high voltage
- low voltage
- low voltage pickup
- low voltage drop out
Battery Information (for batteries 1 through 8)
- Plant voltage
- Measured voltage
- connections corroded
- terminals greased
- signs of leakage
Main Rack
- EAS revision complete
- CSU grounded
- 5 MHz ‘A’ split with ‘T’
- 5 MHz ‘B’ split with ‘T’
T1 Information, Primary and Secondary
- T1 circuit ID#
- T1 surge arrestor installed/grounded
- T1 repeater shelf / cfl cabinet location
- T1 level at extended demarc (RJ48 x jack)
Summary
- log book at site with recent entry
- outstanding issues/punch list items for site
- defective equipment found/replaced
5.5.2 Site As-Built Acceptance Test Procedures
Complete the test procedures described in this section to record the site as built.