Installation manual
IVX 128  Hardware overview/installation 
B.13 
External connections 
Grounding instructions 
IVX grounding (supplemental ground) is as follows: 
•  The conductor wires can be no smaller than the ungrounded branch-circuit supply conductors 
(usually 16-gauge or higher). 
•  Acceptable wire: bare 
or
 covered with green (or green-and-yellow-striped) jacket. 
•  Conductors (and power receptacles) shall connect to earth ground at the service equipment 
(usually a cold water pipe or copper ground rod). 
•  The supplemental ground must: be used regardless of power cord ground, be connected to the 
ground lug on the bottom of the IVX cabinet, and retain ground connection when IVX power sup-
ply module is unplugged. 
•  Connect the grounding lugs of all units to system ground  
Note:
  IVX lines are protected against a 10 KV surge 
only
 if the earth ground procedures described 
above are followed. 
Power 
Each base cabinet requires a 110 VAC outlet (if possible, a dedicated outlet). Use 
only
 the Class-2 
power supply module provided. Expansion Cabinets, as well as the 64-Key Expansion Console, 
require no additional AC power. A clean, isolated power source in conjunction with a UPS is 
STRONGLY
 recommended. Each base cabinet draws a maximum of 25 watts. A fully loaded system 
draws no more than 50 watts. 
If AC power is interrupted, the system will drop all connections. When power is restored, the system 
will resume normal operation in approximately five minutes, having retained its full programming 
and clock setting. 
UPS 
For system protection and to maintain uninterrupted operation, an Uninterruptible Power Supply is 
STRONGLY
 recommended. A UPS rated for 200 VA will provide approximately two hours of uninter-
rupted service for a fully loaded IVX. Every 50 VA of capacity added to the UPS will yield 
approximately one-half hour of additional backup. 










