Technical data

Installation Manual
SYSTEM BOILER – Cod. 99951NA – November 2002
10
0.5
1
1.5
PRESSURE GAUGE
ELECTRONIC WATER
4
5
6
3 2
1
7
AIR VENT
PUMP CUP
AIR VENT VALVE
CIRCULATING PUMP
VALVE CAP
INSTRUMENT PANEL
LEGEND (see fig. 1)
1.
SUMMER-WINTER ON-OFF SWITCH
2.
HEATING TEMPERATURE ADJUSTMENT KNOB
3.
SPACE FOR ADDING AN OPTIONAL TIMER
SELF- DIAGNOSTIC LEGEND (see fig. 2)
4.
WARNING: LACK OF WATER IN THE SYSTEM
5.
WATER PRESSURE LEVEL 1 BAR
6.
WATER PRESSURE LEVEL 1.5 BAR
7.
WARNING: CHIMNEY SAFETY DEVICE
ON R OPEN CHAMBER MODEL
8.
WARNING: LOCK-OUT INDICATOR (FIXED LIGHTS
ONLY – NO FLASHING)
STARTING UP THE BOILER FOR 1
st
TIME
After connecting up the water supply, before starting up the boiler, carry out
the following procedures:
Preliminary procedure
Do as follows:
make sure the power supply for the boiler is the same as that stated on
the plate (230V - 50Hz) and that the live, neutral and earth connections
have been properly connected;
make sure the type of gas being supplied is the same as the type for
which the boiler has been tested and calibrated;
make sure the unit is properly earthed;
make sure there are no flammable liquids or materials in the immediate
vicinity of the boiler;
make sure that any shut-off valves in the heating circuit are open;
open the gas cock and check the gas seals, making sure the counter shows no sign of leaks; in any case, double check by
using a soapy solution and eliminate all eventual leaks. The checking procedure for the gas burner attachment is carried
out with the boiler working;
make sure the electrical mains switch is OFF;
remove the front cover by pulling it forwards;
undo the side screws and rotate the panel downwards
FILLING THE SYSTEM
Fill the heating system as follows, making sure that the gas cock is closed:
open the tap on the filling loop and fill the system until a pressure of 1.5 bar has been reached (light no. 6 fig.2) and then
close the tap;
make sure the cap on the jolly valve is slightly loose to allow air to escape from the system (see fig. 3).
undo the cap on the circulation pump to eliminate any eventual air locks. It is a good idea to purge all radiators of air at this
point too;
before starting up the boiler the water pressure must be checked again; if this is seen to be below 0.5 bar, bring it back up
to 1.5 bar and then close the tap on the filling loop;
switch on the electrical power supply to the boiler;
turn the selector switch to the WINTER position (see fig.1), after a few seconds the pump will come into action;
once the boiler is working, if any noises are heard in the system, repeat the above air purging procedures until there is no
air left in the system;
check there are no obstructions in the exhaust duct;
Fig. 1
Fig. 2
Fig. 3