Connect the cold water pipe to the
storage tank, according to local
regulations and the Plumbing Code.
The hot water line should be
connected to the hot water outlet.

A tempering valve is mandatory.
Ensure it is commissioned correctly.
Incorrect commissioning can lead to
a lack of hot water.
We recommend using an orange
top Reliance brand tempering valve.

A condensation drain line is required
to be tted to carry discharge clear
of water heater.
Condensate drain line should not be
connected to the PTR Valve drain
line but can exit to the same point.

It is recommended that all hot
water lines are insulated with high
temperature, UV resistant 13mm
closed cell insulation.
Installation Instructions
Hot
Tempered
Cold