Technical data

SERVICING
AND
MAINTENAN
CE
INSTRUCTIONS
_
CONDENSING WALL-HUNG BOILER TG05A052.A0205
39
WIRING DIAGRAM FOR REMOTE CONTROL INSTALLATION (no zone valves)
Fit the interface (fig. 2) on the circuit board (fig. 1) into the holes A and B provided (see fig. 1).
Connect plug M1 on the interface circuit board (fig. 2) to plug M11 on the modulation circuit board (fig. 1).
Connect the grey and orange wires in plug M2 of the interface circuit board (fig. 2) and in the terminal block (fig.
4).
Connect the wires of plug M3 on the interface circuit board (fig. 2) in the terminal (fig. 4).
Remove the link TA-TA (fig. 3) and set the boiler to SUMMER mode.
Connect the remote control to the terminal block (fig. 4) using a cable with a minimum section of 2 x 0.5 mm2
section and max. length of 50 m being careful to observe the +/- polarity.
THE EXTERNAL SENSOR IS OPTIONAL. The connection can be made to either the remote control (fig. 5) or to
the terminal block (fig. 3 - dotted line) on the terminals marked SE-SE.
WARNING! The remote control connection cable must pass through a channel which is separate from any system
supplied with power. If this is not possible, fit a screened cable.
M6
M4
M3
M5
M2 M1
M4
M13
M7
M11
M8
M12
M10
M9
EXTERNAL SENSOR
2 M1
1
TELS EXT
IN
-
+
REMOTO
N
L
Se
TA
TA
Se
LINE
Fig. 3
EARTH
NEUTRAL
EXTERNAL
SENSOR
ROOM
THERMOSTAT
5+V Z
Fig. 4
4-
RL1
orange
grey
M3
M2
7 8
Fig. 2
M1
Interfaccia
A
13
EXTERNAL SENSOR DIAGRAM FOR CORRECTION OF HEATING FLOW TEMPERATURE
ACCORDING TO THE EXTERNAL TEMPERATURE AND CURVE SETTING
TM - MAX / MIN = Range of heating flow temperature
Te = external temperature
Tm = heating flow temperature
A = standard heating temperature
B = reduced heating temperature
70
35
MIN
25
2726
30
30
35
45
40
50
60
55
65
192425 23 2122 20 161817 1514
Tm
MAX40 80
75
-12101211 89 7 56 4 23 1 -6-3-10 -2 -4-5 -9-7-8 -10-11
8
9
7
6 5
0
Te (°C)
-15-13-14
1
2
3
4
Fig. 1
Fig. 5
P.B.C.
INTERFACE
REMOTE
B
A B