Technical data

SERVICING
AND
MAINTENAN
CE
INSTRUCTIONS
_
CONDENSING WALL-HUNG BOILER TG05A052.A0205
31
D
B
10
20
30
40
A
MANOMETRO
C
Parameter 11 setting: MAXIMUM HEATING OUTPUT SETTING
To check or modify the existing pressure value:
a. Insert a manometer into the gas valve pressure point B (fig.1);
b. Put ON/OFF button
1
in OFF position ( );
c. Push pad
6
and
4
simultaneously and keep them pressed;
d. Put ON/OFF button 1 in ON position ( ) and wait until the
display shows - ;
e. Release pad 6 and 4 ;
f. Keeping service pad
5
pressed, press pad
6
and select parameter no. ;
g. Release service pad
5
press and release service pad
5
;
h. The display will show the parameter value to be set or modified;
i. Press pad
6
to increase or pad
4
to decrease gas pressure according to heating system kW (output) requirement as per table
1 (the gas pressure value will be displayed in the manometer);
j. Once the required pressure has been reached, press and release service pad
5
, the display ill show value ;
u. Position the ON/OFF button 1 in OFF position ( )
k. Remove the silicon pipe from the pressure point B (fig.1), close tigly the pressure point screw and make sure there are no gas leaks;
l. Put the ON/OF button in ON position ( );
Gas valve VK 4105G
Fig. 1
P
0
1
1