Technical data

SERVICING
AND
MAINTENAN
CE
INSTRUCTIONS
_
CONDENSING WALL-HUNG BOILER TG05A052.A0205
29
D
10
20
30
40
MANOMETRO
9: MECHANICAL MINIMUM GAS PRESSURE SETTING
The mechanical minimum gas pressure is factory calibrated on all boilers at 17/18 mmH20.
When replacing the gas valve adjust the mechanical minimum pressure as
follows: :
Using a single cut screwdriver turn D screw (fig.1 ) clockwise and
tight it ;
To adjust the mechanical minimum, turn D screw (fig.1)
counter-clockwise for two complete turns.
Parameter
10
setting: MINIMUM HEATING OUTPUT SETTING
To check or modify the existing pressure value:
a. insert a manometer into the gas valve pressure point B (fig.1);
b. Put ON / OFF button
1
in OFF position ( );
c. Push pad 6 and 4 simultaneously and keep them pressed;
d. Put ON / OFF button
1
in ON position ( ) and wait until the display shows - ;
e. Release pad
6
and
4
;
f. Keeping pad5 pressed, press pad 6 and select parameter no. ;
g. Release service pad
5
, press and release service pad
5
;
h. The display will show the parameter value to be set or modified;
i. The manometer inserted in the pressure point B (fig. 1) will show the minimum gas pressure;
j. If that value is different than the one stated on the data plate, modify it by pressing pad
6
to increase or pad
4
to decrease
gas pressure;
k. Push service pad
5
to confirm the setting; display will show parameter no. ;
l. Once the minimum gas pressure has been adjusted, switch the boiler OFF by putting ON / OFF button 1 in OFF position ( );
m. Remove the silicon pipe from the pressure point B (fig.1), close tightly the pressure point screw and make sure there are no gas leaks;
n. Position the ON / OFF button
1
in ON position ( );
Gas valve VK 4105G
P
0
1
Fig. 1
1