CONDENSING WALL-HUNG BOILER TG05A052.A0205
OVERALL DIMENSIONS - FLUE KIT H
KIT H: for the exhaust of combustion
products and air intake through the twin
pipes Ø80mm/80mm.
When deciding the Flue Length:
consider the total length of flue starting
by the room-seal chamber top
connection excluding the first bend.
The use of additional bends reduce
linear length by the following value:
90° flue bend Ø80(wide radius) = 1.5 m.
90° flue bend Ø80(narrow radius) = 3 m
45° flue bend Ø80 (wide radius)= 1.2 m.
Total length of flue =
1) linear length of flue pipes +
2) value of additional bends used
N.B.: For the twin pipe flue kit, the
maximum length of the exhaust pipe
must not exceed 2/3 of the maximum
length as shown in the table on page 8.