INSTALLATION, AND MAINTENANCE MANUAL FOR GAS FIRED, CONDENSING BOILERS model RH 28 TYPE C HEATING ONLY - ROOM SEALED model RHR 28 TYPE C COMBI - ROOM SEALED SEDBUK BAND B CE 0694 RADIANT BRUCIATORI S.p.A. Montelabbate (PU) ITALY TG05A052.
CONTENTS INSTALLATION INSTRUCTIONS PRODUCT CONFORMITY page 1 INSTALLATION INSTRUCTIONS AND WARNINGS page 2 TECHNICAL DATA page 4 OVERALL DIMENSIONS page 5 FLUE OPTIONS – FLUE KIT INSTALLATION INSTRUCTION page 6 GENERAL INSTALLATION REQUIREMENTS page 12 BOILER INSTALLATION page 16 ELECTRICAL CONNECTIONS page 18 BOILER CONTROL PANEL page 19 COMMISSIONING page 19 BOILER CONTROL PANEL page 21 TECHNICAL SPECIFICATIONS page 22 MULTIGAS OPERATION page 32 GAS PRESSURE SETTING
INSTALLATION INSTRUCTIONS_ HEATING TECHNOLOGY SINCE 1959 Thank you for choosing RADIANT Declaration for purposes of Art. 7 of Law 46 of 5 April 1990. RADIANT BRUCIATORI S.p.A. hereby declares that all of its products are constructed to industry standards as required by the Article in question and by Article 5 of the law in effect (D.P.R. no. 447/97).
INSTALLATION INSTRUCTIONS_ INSTALLATION INSTRUCTIONS - WARNINGS THIS INSTALLATION, USE, AND MAINTENANCE MANUAL IS AN ESSENTIAL AND INTEGRAL PART OF THE PRODUCT, AND MUST ALWAYS BE KEPT NEAR THE DEVICE. THE WARNINGS CONTAINED IN THIS SECTION ARE ADDRESSED BOTH TO THE USER AND TO INSTALLATION AND MAINTENANCE PERSONNEL. THE USER WILL FIND INFORMATION ON OPERATION AND LIMITS OF USE IN THE ACCOMPANYING MANUAL, WHICH SHOULD BE READ VERY CAREFULLY. STORE THE MANUAL CAREFULLY FOR FUTURE REFERENCE.
INSTALLATION INSTRUCTIONS_ SYSTEMS WITH THERMOSTATS A by-pass must be installed in heating systems with radiators thermostats. As required by current norms, these devices must be installed by qualified personnel only, who must respect norms UNI-CIG 7129 and 7131 and revisions, fire department regulations, and requirements of the local gas company. Before installing the boiler, make sure that the water and heating systems are compatible with its output.
INSTALLATION INSTRUCTIONS_ TECHNICAL DATA Type C unit Type C devices are devices in which the combustion circuit (air intake, combustion chamber, exchanger, combustion exhaust) is sealed off from the place where they are installed. RH 28 0694BN3485 RHR 28 0694BN3485 kW Btu/h kW Btu/h kW C12 C32 C42 C52 C82 26.80 91495 20 68280 27.47 C12 C32 C42 C52 C82 26.80 91495 20 68280 27.47 Btu/h % % kW Btu/h kW Btu/h 93783 102.50 100.80 25.51 87103 19.02 64934 93783 102.50 100.80 25.51 87103 19.
INSTALLATION INSTRUCTIONS_ OVERALL DIMENSIONS 450 830 160 S R C 70 F 80 A 130 102 55.5 325 325 224 156 64.5 78 G 104 226 KEY R RETURN ¾” G GAS ½” C HOT WATER ½” F COLD WATER ½” A HEATING FLOW ¾” CONDENSING WALL-HUNG BOILER – TG05A052.
INSTALLATION INSTRUCTIONS_ kit K - Horizontal-coaxial flue kit system with intake / exhaust pipes Ø100/60 Diaphragms system NUMBERS FOR ADJUSTMENT LOWER DISC INDICATOR UPPER DISC 2 1 3 4 5 INDICATOR UPPER DISC NUMBERS FOR ADJUSTMENT LOWER DISC N.B.: SEMI-PUNCHED TAGS ON BOTH UPPER AND LOWER DISC Diaphragms system setting – Maximum flue length : 3 mt. indicator ⇒ 1 1.1 1.2 1.3 2 2.1 2.2 2.3 3 3.1 3.2 3.3 4 4.1 4.2 4.3 5 No diaphragm models ⇓ ( ) RH 28 – RHR 28 * from 2 from 0.
INSTALLATION INSTRUCTIONS_ 450 100 60 100 KIT K: for the exhaust of combustion products and air intake through the 2 coaxial pipes, Ø100mm. external pipe (air intake) and Ø60mm. internal pipe (flue exhaust) to an external wall or a combined flue duct (chimney) conforming to UNI 7129/01 standard and D.P.R.
INSTALLATION INSTRUCTIONS_ kit H - Twin pipe flue kit system with intake/exhaust pipes ø80/80 Diaphragms system NUMBERS FOR ADJUSTMENT LOWER DISC INDICATOR UPPER DISC 1 2 3 INDICATOR UPPER DISC NUMBERS FOR ADJUSTMENT LOWER DISC Diaphragms system setting – Maximum flue length : 30 mt. Indicator ⇒ 1 1.1 1.2 from 1 to 8 mt from 8 to 18 mt 1.3 2 2.1 2.2 2.3 3 No diaphragm models ⇓ RH 28 – RHR 28 Example : from 18 to 30 mt intake/exhaust pipes length (equivalent length): 2.
INSTALLATION INSTRUCTIONS_ OVERALL DIMENSIONS - FLUE KIT H 80 80 160 105 224 951 The use of additional bends reduce linear length by the following value: 90° flue bend Ø80(wide radius) = 1.5 m. 90° flue bend Ø80(narrow radius) = 3 m 45° flue bend Ø80 (wide radius)= 1.2 m. 830 When deciding the Flue Length: consider the total length of flue starting by the room-seal chamber top connection excluding the first bend.
INSTALLATION INSTRUCTIONS_ kit V - Horizontal-coaxial flue kit system with intake / exhaust pipes Ø100/60 Diaphragms system NUMBERS FOR ADJUSTMENT LOWER DISC INDICATOR UPPER DISC 1 2 3 4 5 INDICATOR UPPER DISC NUMBERS FOR ADJUSTMENT LOWER DISC N.B.: SEMI-PUNCHED TAGS ON BOTH UPPER AND LOWER DISC Diaphragms system setting – Maximum flue length : 3 mt. indicator ⇒ 1 1.1 1.2 1.3 2 2.1 2.2 2.3 3 3.1 3.2 3.3 4 4.1 4.2 4.3 5 No diaphragm models ⇓ ( ) RH 28 – RHR 28 * from 2 from 0.
INSTALLATION INSTRUCTIONS_ OVERALL DIMENSIONS - FLUE KIT V KIT V = for the exhaust of combustion products and air intake through the 2 coaxial pipes, Ø100mm. external pipe (air intake) and Ø60mm. internal pipe (flue exhaust) to the roof conforming to UNI 7129/01 standard and D.P.R. 412/93 When deciding the Flue Length, consider the total length of flue starting by the room-seal chamber top connection. The use of additional bends reduce linear length by the following value: 90° flue bend Ø100/60 = 0.8 m.
INSTALLATION INSTRUCTIONS_ GENERAL INSTALLATION REQUIREMENTS GAS SAFETY It is the law that all gas appliances are installed by a CORGI registered installer (you can check this by contacting corgi on 01256.372200) in accordance with the regulations listed below. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the law is complied with.
INSTALLATION INSTRUCTIONS_ FLUE POSITION IMPORTANT: THE FLUE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE RECOMMENDATIONS CONTAINED IN BS 5440:1. The boiler MUST be installed so that the terminal is exposed to the external air. It is important that the position of the terminal allows free passage of air across it at all times. If the terminal discharges into a pathway or passageway check that combustion products will not cause nuisance and that the terminal will not obstruct the passageway.
INSTALLATION INSTRUCTIONS_ CENTRAL HEATING SYSTEM -Fig. 1 The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS 5449 and BS 6798. The system should be designed to operate with flow temperatures of up to 82°C. When designing the system, the pump head, expansion vessel size, mean radiator temperature, etc. must all be taken into account. Refer to the pump performance table for guidelines.
INSTALLATION INSTRUCTIONS_ CONDENSATE DRAIN Termination to an internal soil and vent pipe FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run. Boiler 50m m per m etre o 2 .5 ° M f p ip e inim um run fall I.
INSTALLATION INSTRUCTIONS_ BOILER INSTALLATION MINIMUM DISTANCES FOR FIXING TO WALL To allow access in the boiler for maintenance operations, the minimum distances shown below must be respected (fig. 1): To facilitate installation, the boiler is supplied with a template for advance location of connections to pipes. In this way, you may simply hook up the boiler when wall work is completed. 60 S MINIMUM DISTANCE mm. Fig.
INSTALLATION INSTRUCTIONS_ ANTI-FREEZE SYSTEM ANTI-FROST SYSTEM Radiant boilers are equipped with an AntiFreeze system which comes into operation when the temperature falls to 5° C (Heating sensor) and 4° C (Hot water sensor). To protect the internal Radiators, a room thermostat or remote control must be fitted.
INSTALLATION INSTRUCTIONS_ ELECTRICAL CONNECTIONS For qualified personnel only: the boiler works with 230 V 50 Hz AC current and has maximum input of 170 W. Connection to the electrical mains must be performed with a device having an omnipolar opening of at least 3 mm. Make sure the live and neutral connections conform to the diagram. A secure earth connection is compulsory according to national and local ragulations.
SERVICING AND MAINTENANCE INSTRUCTIONS_ CONTROL PANEL KEY TO CONTROLS (fig. 1) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14.
SERVICING AND MAINTENANCE INSTRUCTIONS_ • close the T cap and connect the pipe P to the discharge pipe; AIR VENT VALVE CAP Starting up the boiler • turn on the gas cock situated under the boiler grill; • set the ON/OFF button (1) (see fig.1 pag. 19) to ON position ; • make sure that no flashing value is on the display (14); if value 04 is flashing and no.8 light is ON it means water deficiency in the system: open the filling tap on the filling loop and fill the system until a pressure of 1.
SERVICING AND MAINTENANCE INSTRUCTIONS_ CONTROL PANEL 1 ON / OFF POWER BUTTON 13 WATER DEFICIENCY INDICATOR 2 HEATING TEMPERATURE ADJUSTMENT KNOB 12 WATER PRESSURE LEVEL 1 BAR INDICATOR 3 DOMESTIC HOT WATER TEMPERATURE ADJUSTMENT KNOB 11 WATER PRESSURE LEVEL 1.
SERVICING AND MAINTENANCE INSTRUCTIONS_ DIAGNOCODE SM 20015 ELECTRONIC PRINTED CIRCUIT BOARD cod. 76655LA M9 M10 M11 M8 M12 M13 M7 M6 M5 M4 M3 M2 M1 TECHNICAL SPECIFICATION New generation printed circuit board with easy settings of boiler parameters.
SERVICING AND MAINTENANCE INSTRUCTIONS_ FUNCTIONS CODES CODE TYPE OF FUNCTION 7 CHIMNEY-SWEEPER FUNCTION ON 8 ANTI-FROST FUNCTION HEATING CIRCUIT 9 ANTI-FROST FUNCTION DOMESTIC HOT WATER CIRCUIT 13 28 31 DESCRIPTION THE CHIMNEY-SWEEPER FUNCTION IS ACTIVATED BY KEEPING PRESSED "SERVICE" PAD FOR 5 SECONDS. TO CANCEL IT RESET THE UNIT BY PUSHING ON/OFF BUTTON. THIS FUNCTION BRINGS THE UNIT TO THE MAX HEATING GAS PRESSURE FOR 15 MINUTES WITHOUT MODULATING DOWN.
SERVICING AND MAINTENANCE INSTRUCTIONS_ PARAMETERS TABLE PARAMETER NUMBER TYPE OF OPERATION PARAMETER VALUE 0 BOILER TYPE SELECTION 00 v 01 1 BOILER TYPE SELECTION 00 01 02 2 GAS TYPE SELECTION 3 4 5 6 7 8 9 10 11 HEATING TEMPERATURE SETTING PUMP SETTING IN HEATING MODE WATER-HAMMER PREVENTION SETTING SHORT CYCLING FUNCTION HEATING CIRCUIT (FACTORY CALIBRATED AT 180” PARAMETER VALUE “36” ) PUMP OVERRUN HEATING CIRCUIT (FACTORY CALIBRATED AT 180”PARAMETER VALUE “36” ) PUMP OVERRUN DOM.
SERVICING AND MAINTENANCE INSTRUCTIONS_ 1 Parameter setting: BOILER TYPE SELECTION To modify the Parameter value: a. Put ON/OFF button 1 in OFF position ( b. Push pad 6 simultaneously and keep them pressed; and 4 in ON position ( c. Put ON/OFF button 1 d. Release pad 6 e. Keeping pad 5 and 4 h. Press pad 6 02 ) and wait until the display shows and select parameter no.
SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter 3 setting: HEATING TEMPERATURE SETTING To modify the Parameter value: a. Put ON/OFF button 1 in OFF position ( b. Push pad 6 simultaneously and keep them pressed; and 4 c. Put ON/OFF button 1 in ON position ( d. Release pad 6 and 4 ; e. Keeping pad 5 pressed, press pad 6 f. Release service pad 5 g. The display ); P )and wait until the display shows and select parameter no.
SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter 5 setting: WATER-HAMMER PREVENTION SETTING To modify the Parameter value: a. Put ON/OFF button 1 in OFF position ( b. Push pad 6 simultaneously and keep them pressed; and 4 c. Put ON/OFF button 1 in ON position ( d. Release pad 6 and 4 ; e. Keeping pad 5 pressed, press pad 6 f. Release service pad 5 g. The display and select parameter no.
SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter 7 setting: PUMP OVERRUN - HEATING CIRCUIT adjustable from 0 to 7.5 minutes. Factory calibrated at 3 minutes STANDBY. (N.B. DO NOT set the overrun time under 3 minutes) To modify the Parameter value: a. Put ON/OFF button 1 in OFF position ( b. Push pad 6 simultaneously and keep them pressed; and 4 c. Put ON/OFF button 1 in ON position ( d. Release pad 6 and 4 ; e. Keeping pad 5 pressed, press pad 6 f. Release service pad 5 g. The display h.
SERVICING AND MAINTENANCE INSTRUCTIONS_ 9: MECHANICAL MINIMUM GAS PRESSURE SETTING The mechanical minimum gas pressure is factory calibrated on all boilers at 17/18 mmH20. When replacing the gas valve adjust the mechanical minimum pressure as follows: : • Using a single cut screwdriver turn D screw (fig.1 ) clockwise and 40 tight it ; • 30 To adjust the mechanical minimum, turn D screw (fig.1) D 20 counter-clockwise for two complete turns.
SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter 11 setting: MAXIMUM GAS PRESSURE SETTING - MAXIMUM HEATING OUTPUT SETTING To check or modify the existing pressure value: a. Insert a manometer into the gas valve pressure point B (fig.1); b. Put ON / OFF button 1 in OFF position ( B ); A C 40 30 c. Push pad 6 and 4 simultaneously and keep them pressed; D 20 d. Put ON / OFF button 1 display shows P - in ON position ( 0 MANOMETRO and 4 f. Keeping pad 5 pressed, press pad 6 h.
SERVICING AND MAINTENANCE INSTRUCTIONS_ Parameter 11 setting: MAXIMUM HEATING OUTPUT SETTING To check or modify the existing pressure value: b. Put ON/OFF button1 in OFF position ( A B a. Insert a manometer into the gas valve pressure point B (fig.1); C 40 ); 30 c. Push pad 6 and 4 simultaneously and keep them pressed; D 20 10 d. Put ON/OFF button 1 display shows P in ON position ( - 0 ) and wait until the ; MANOMETRO Fig. 1 e. Release pad 6 and 4 ; f.
SERVICING AND MAINTENANCE INSTRUCTIONS_ CONVERSION OF GAS TYPE 10 8 Conversion of the boiler from natural gas to LPG and viceversa must be performed by qualified personnel only. Conversion is performed as follows: a. Isolate the boiler from mains b. c. • • • • d. e. 8 7 7 9 3 11 9 6 6 2 electricity supply 4 3 Close the boiler gas service 5 cock 1 replace jets on the main Fig. 1 burner as follows: undo the gas pipe 6 (fig.1) from the burner manifold LEGEND: using a size 24 spanner; 1.
SERVICING AND MAINTENANCE INSTRUCTIONS_ GAS DATA TABLE models: RH 28 – RHR 28 Lower Wobbe index (15°C; 1013 mbar) MJ/Nm3 Natural Gas G 20 Liquid Butane Gas G 30 Liquid Propane Gas G 31 45.67 80.58 70.69 Rated feed pressure mbar 20 30 37 Minimum feed pressure mbar 17 28 28 Main burner: 13 Jets - Ø jet mm 1.25 0.77 0.77 Consumption (15°C; 1013 mbar) m3/h 2.84 - - Consumption (15°C; 1013 mbar) kg/h - 1.78 1.
SERVICING AND MAINTENANCE INSTRUCTIONS_ MAIN COMPONENTS – mod. RH 28 17 16 2 16 3 15 11 5 4 6 15 11 4 2 7 13 12 RIGHT VIEW FRONT VIEW LEFT VIEW 10 9 14 HYDRAULIC DIAGRAM 1 18 17 2 16 1 TOP VIEW POS. CODE 1 95019LA LT.
SERVICING AND MAINTENANCE INSTRUCTIONS_ MAIN COMPONENTS – mod. RHR 28 20 19 2 19 3 18 12 5 4 6 18 12 4 2 11 16 17 22 RIGHT VIEW FRONT VIEW 7 14 LEFT VIEW 12 10 9 15 HYDRAULIC 1 21 20 2 19 1 TOP VIEW POS.. CODE 1 95019LA .8 LT.
SERVICING AND MAINTENANCE INSTRUCTIONS_ LIMITER The boiler is equipped with a variable flow limiter at the cold water inlet. The flow limiter can be adjusted by turning the screw in order to obtain the correct flow rate of domestic hot water for the specific boiler output. FLOWSWITCH This device gives precedence to domestic hot water and is fitted to boilers which supply instantaneous hot water. It allows conversion to hot water even with a minimum hot water demand (min.
SERVICING AND MAINTENANCE INSTRUCTIONS_ WIRING DIAGRAMS – mod. RH 28 PRINTED CIRCUIT BOARD CVI-M SM20015 (cod. 76655LA) DISPLAY DIGITAL BOARD 2000 SKO6206 (COD. 76654LA) M9 M10 M11 M8 M12 M13 M7 M6 M5 M4 M3 M2 M1 KEY TA EA ER EV SF ELECTRONIC IGNITION BOARD CVI S4565 A 2019B (COD.
SERVICING AND MAINTENANCE INSTRUCTIONS_ WIRING DIAGRAMS – mod. RHR 28 PRINTED CIRCUIT BOARD CVI-M SM20015 (cod. 76655LA) DISPLAY DIGITAL BOARD 2000 SKO6206 (COD. 76654LA) M9 M10 M11 M8 M12 M13 M7 M6 M5 M4 M3 M2 M1 KEY L N PA PAC MF IG SS SR C TS SE ELECTRONIC IGNITION BOARD - LINE CVI S4565 A 2019B (COD. 76631LA) - NEUTRAL 12 11 10 9 8 7 6 5 4 3 2 1 - AIR PRESSURE SWITCH LM - WATER PRESSURE SWITCH ER EA - ELECTRONIC FLOWSWITCH + PWM Bloc - MAIN SWITCH N RT - D.H.
SERVICING AND MAINTENANCE INSTRUCTIONS_ WIRING DIAGRAM FOR REMOTE CONTROL INSTALLATION (no zone valves) RL1 EXTERNAL SENSOR M13 grey orange N 7 8 P.B.C. INTERFACE REMOTE Z 5+ 4- Se Se TA M3 Fig. 2 V L M1 Interfaccia ROOM THERMOSTAT M12 NEUTRAL LINE M8 EARTH M11 Fig. 3 M9 M10 B M2 A Fig. 4 TA M7 EXTERNAL SENSOR M6 M1 1 2 M5 S EXT TEL - IN + M4 M3 M2 REMOTO Fig. 5 M1 M4 Fig. 1 Fit the interface (fig. 2) on the circuit board (fig.
SERVICING AND MAINTENANCE INSTRUCTIONS_ MAINTENANCE To keep the boiler in efficient and safe operating condition, we recommend you perform the following checks at least once a year: • Check all seals on the gas side and replace gaskets to restore perfect seal as required. • Check all seals on the water side and replace gaskets to restore perfect seal as required. • Visually check combustion and the combustion chamber; dismantle and clean the chamber if necessary.
SERVICING AND MAINTENANCE INSTRUCTIONS_ Fault Code Description Possible Cause Solution BOILER FAILS TO FIRE a. No gas / gas turned off 01 Flame lock-out a. b. c. d. e. Ignition electrode damaged or earthed Electronic ignition board S4565QM faulty Gas valve faulty Minimum mechanical gas setting too low (onto the gas valve) or slow ignition f. Inlet gas pressure excessive (only for LPG boilers) g. Condensate trap obstructed b. c. d. e. f.
SERVICING AND MAINTENANCE INSTRUCTIONS_ SPARE PARTS SHORT LIST CODE DESCRIPTION RH 28 RHR 28 √ 20047LA PLATE EXCHANGER 20 P 17B1902006 21001LA GAS BURNER 13 RAMP 1.25 NATURAL GAS 401.1207.02 √ √ 21004LA GAS BURNER 13 RAMP 0,77 L.P.G. 401.1207.05 √ √ 24029LA CIRCULATING PUMP MOTOR SHUL CLF6 15/6 √ √ 24046LA CIRCULATING PUMP RSL 15/6-3-KUCLF6 W/C1 √ √ 27044LA CONDENSATE TRAP √ √ 35007LA IGNITION ELECTRODE E.
SERVICING AND MAINTENANCE INSTRUCTIONS_ MULTIPLEX - SPARE PARTS SHORT LIST 43150LA 43139LA 64066LA 54022LA 89116NA 89116NA 64093LA 64065LA 43135LA 20047LA 64068LA 61004LP 89122NA 89122NA 43145LA 43150LA 43150LA 43151LA 64063LA 64075LA 54023LA 64060LA 43139LA 43139LA 43150LA 54022LA 43139LA 54024LA 89134NA 43151LA 43151LA 54022LA 54022LA 64103LA 43150LA 54022LA 43150LA 43159LA 96034LA 96032LA 64067LA 54022LA 43150LA 64072LA 43150LA 54022LA 43150LA 89134NA 64083LA 59015LA 73507LA 89126NA 4
RADIANT BRUCIATORI s.p.a. Via Pantanelli, 164/166 - 61025 Loc. Montelabbate (PU) Tel. +39 0721 9079.1 • fax. +39 0721 9079279 e-mail: info@radiant • Internet: http: www.radiant.it UK – Radiant Helpline – 01329.828555 ALL DESCRIPTIONS AND ILLUSTRATIONS CONTAINED IN THIS LEAFLET HAVE BEEN CAREFULLY PREPARED BUT WE RESERVE THE RIGHT TO MAKE CHANGES AND IMPROVEMENTS IN OUR PRODUCTS WHITCH MAY AFFECT THE ACCURANCY OF THE INFORMATION CONTAINED IN THIS LEAFLET. E + OE ALL RIGHTS RESERVED.
USER MANUAL model RH 28 TIPO C ONLY SYSTEM - ROOM SEALED model RHR 28 TIPO C SYSTEM - ROOM SEALED CE 0694 Technical Specification RADIANT BRUCIATORI S.p.A. Montelabbate (PU) ITALY TG05B052.
User Manual BOILER OPERATION AND ADJUSTMENT PROCEDURES FOR USER Before turning on the boiler read the following warnings carefully . Make sure that the warranty booklet carries the stamp of the CORGI registered technician (you can check this by contacting corgi on 01256.372200) responsible for installing the boiler. Installation, starting up for the first time, adjustments and maintenance operations must all be carried out solely by qualified technicians.
User Manual Turning off boilers with electronic ignition : • turn selector switch 1 to the OFF position (see fig. 1 pag. I).; • if the boiler will not be used for long periods it is recommended that the gas cock under the boiler grill be shut off. THE BOILER IN USE Summer-winter use (see fig. 1 pag. I). Push Pad 5 (fig.
RADIANT BRUCIATORI s.p.a. Via Pantanelli, 164/166 - 61025 Loc. Montelabbate (PU) Tel. +39 0721 9079.1 • fax. +39 0721 9079279 e-mail: tecnico@radiant • Internet: http://www.radiant.it UK – Radiant Helpline – 01329.828555 ALL DESCRIPTIONS AND ILLUSTRATIONS CONTAINED IN THIS LEAFLET HAVE BEEN CAREFULLY PREPARED BUT WE RESERVE THE RIGHT TO MAKE CHANGES AND IMPROVEMENTS IN OUR PRODUCTS WHITCH MAY AFFECT THE ACCURANCY OF THE INFORMATION CONTAINED IN THIS LEAFLET. E + OE ALL RIGHTS RESERVED.