CONDENSING BOILOES WITH STORAGE - TG05A095.A0306
44
6.3 Maintenance for unvented components
It is essential that the unvented hot water components have a regular maintenance programme. It is Radiant’s
recommendation that this be carried out in conjunction with the annual boiler service.
The
STORAGE CYLINDER and CENTRAL HEATING PRESSURE RELIEF VALVES should be manually operated for a
period of not less than 5 seconds each to:
i. Check the flow of water through the valve and the final discharge route to the drain.
ii. Check the relief valves reseat property.
The
DHW EXPANSION VESSEL pre-set pressure should be checked as follows,
i. Close main stopcock;
ii. Relieve pressure from system by opening a hot tap
iii. Check pressure of vessel using an accurate type pressure gauge;
iv. Adjust if necessary to 3.5 bar (with car foot pump);
The
INLET CONTROL GROUPS FILTER should be checked for blockages as follows,
i. Close main stopcock;
ii. Relieve system pressure by opening a hot tap;
iii. Disconnect and remove pressure-reducing valve from the inlet group;
iv. Clean inlet filter; replace it and test;
v. Open main stopcock;
Check the
SACRIFICIAL ANODE located at the top of the storage cylinder by using the easy test nipples as
follows:
i. Unscrew the red cap located on the top of the anode;
ii. If water is released the anode requires replacing;
iii. If no water is released then the anode is still serviceable ensure the red cap is screwed down tightly and noted
on the service record as checked.