Instruction manual

REGULATION INSTRUCTIONS
CONDENSING BOILOES WITH STORAGE - TG05A095.A0306
38
PARAMETER N° 7 – CENTRAL HEATING PUMP
OVERRUN
7. Use () and () buttons to modify the value of the
parameter:
00 = 0
99 = 99 x 5’’ = 450 ‘’ = 7.5’
Default value is set to 36 = 180’’ = 3’
8. Press and release the service (
S) button to confirm
your choice. Number 7 will appear on the display;
9. If you have to modify some other parameter, follow
the 4 – 5 steps (p. 35), then go to the specific procedure
for that parameter, otherwise switch off and on the
appliance to register the modifications.
PARAMETER N° 8 – D.H.W. PUMP OVERRUN
7. Use () and () buttons to modify the value of the
parameter:
00 = 0
99 = 99 x 5’’ = 450 ‘’ = 7.5’
Default value is set to 18 = 90’’ = 1.5’
8. Press and release the service (
S) button to confirm
your choice. Number 8 will appear on the display;
9. If you have to modify some other parameter, follow
the 4 – 5 steps (p. 35), then go to the specific procedure
for that parameter, otherwise switch off and on the
appliance to register the modifications.
PARAMETER N° 9 – MINIMUM GAS RATE ON D.H.W.
7. The value of the parameter must be equal to the one
shown into page 34 table.
Use () and () buttons to set the parameter to the
default value of
20 both for Natural Gas & L.P.G..
8. Press and release the service (
S) button to confirm
your choice. Number 9 will appear on the display;
9. If you have to modify some other parameter, follow
the 4 – 5 steps (p. 35), then go to the specific procedure
for that parameter, otherwise switch off and on the
appliance to register the modifications.
S
S
36
7
8
18
S
S
S
S
9
20