REGULATION INSTRUCTIONS
CONDENSING BOILOES WITH STORAGE - TG05A095.A0306
35
5.2 Parameters programming
5.2.1 Entering Parameters Menu
Each time you wish to change or check any parameter value, you should access the parameter menu, following
this procedure:
1. Place the ON/OFF switch in OFF position;
2. Keep pressed the (▲) and (▼) buttons, switch on the boiler
and wait for the display to show ‘PL’ – ‘0’;
3. Release (▲) and (▼) buttons;
4. Keeping the ‘service’ (
S) button pressed, use the (▲) or (▼)
buttons to choose the parameter you wish to change or
check. Parameter number will be shown on the display;
5. Release the service (
S) button, then re-press and release
it. On display you may read the parameter value;
6. If needed, change the value accordingly with the
following procedures (one for each parameter), otherwise,
switch off and then on the appliance to reset and restart
the boiler.