Specifications

Chapter 4 Supervisory Port Software Configuration Optimux-XLT1 Installation and Operation Manual
4-20 The Optimux-XLT1 Interface
Changing the Configuration of the Serial Port
To change the configuration of the serial port:
1. Type 4 in the Interface Menu screen.
The Serial Port Configuration screen appears.
LOCAL DEVICE
SERIAL PORT CONFIGURATION
-------------------------
0. Exit.
1. Baud rate. 38400 baud
2. parity. NO
Enter your choice:
2. Type 1 to set the baud rate
3. Type 4 for 9600, 6 for 19200, 7 for 38400, 8 for 57600, or 9 for 115200 bps.
4. Type 2 to set the parity
5. Type 0 for no parity, 1 for even, or 2 for odd.
6. Confirm the action.
7. Type 0 to exit the Serial Port Configuration screen.
Resetting to the Default Configuration
To reset all T1 and fiber optic interfaces to "Normal" operation:
1. Type 5 in the Interface Menu screen.
The Set Configuration to Default screen appears.
LOCAL DEVICE
SET CONFIGURATION TO DEFAULT
----------------------------
NOTE: After performing this operation all interfaces
will be set to NORMAL configuration.
0. Exit
1. Reset to default configuration
Enter your choice: 1
Type 'reset' to confirm reset to default setting, ESC to cancel:
reset
All interfaces have been set to default!
2. Type 1 to perform the reset to default configuration option.
3. Type reset to confirm or press ESC to cancel your choice.
4. Type 0 to exit the Set Configuration to Default screen.