System information

Chapter 2 Agent Configuration Mode RADview-PC/TDM Megaplex-2100/2104 User’s Manual
Parameter Possible Values / Remarks
Filter Set Filter set limit. The filtered alarm is active if:
A state alarm is in the ON state for more than the specified percentage of the time
defined by the Filter Window 0% to 100%
An event occurs more than the specified number of times during the time defined by the
Filter Window 0 to 255 times
Note: The Filter Set limits must be greater than the Filter Reset limits. If a state alarm or
event occurs between the F. Set and F. Reset limits, the alarm's status remains unchanged
Filter Reset Filter reset limit. The filtered alarm is not active if:
A state alarm is in the ON state for less than the specified percentage of the time defined
by the Filter Window 0% - 100%
An event occurs less than the specified number of times during the time defined by the
Filter Window 1 - 255 times
[Add…] Click <Add…> to open Add Alarm Attributes dialog box. Add a new set of alarm
attributes and click <Set>.
[Change…] Select an entry in the table and click <Change…> to open Change Alarm Attributes
dialog box. Change alarm attributes and click <Set>.
[Reset] Select an entry in the table and click <Reset> to can reset the attributes of an alarm
type to their default values. The Reset operation removes any filters, sets Invert to No,
and sets Mask to No and Save. If the alarm is not active, it will be removed from the
Alarm Attributes table.
Sorting Alarm Attributes
If the Alarm Attributes list contains at least two entries, you can display entries
according to alarm level type.
To sort the alarm attributes
1. In the Level group of the Alarm Attributes dialog box, select the alarm level
type that you want to display. The available options are: All, System only,
Card and ports and Port.
2. If the alarm level type is Card and ports or Port, select a slot. The available
options are PS-A, PS-B, CL-A, CL-B, IO-1 to IO-12 and All.
3. If the alarm level type is Port, select a port. The available options are:
external-1 to external-12, internal-1 to internal-12 and All.
4. Click <Apply>. The alarm types that match the selected level appear in the
Alarm Attributes table.
To display attributes of all alarms in the selected level in the Alarm Attributes
table:
In the Attributes group, select All. Click <Apply>.
2-34 Megaplex Level Fault Operations