Specifications
Chapter 2 Module Installation and Operation Installation and Operation Manual
2-4 Installing and Connecting the Protection Switch DXC-100PSX
5. Connect another BNC cable (CBL-100PSX-DE3T3) between the TX port of the
DXC-100PSX Broadband Redundant module and the RX port of the
corresponding backup broadband interface module in the DXC-100.
4
Figure
2-3
illustrates a DXC-100PSX connection for Broadband Redundancy.
DXC-100
Figure
2-3. DXC-100PSX Broadband Cable Installation
In the above figure, slot 9 contains a Broadband Group 1 primary interface
module, and slot 11 contains the Broadband Group 1 backup module. Slots 2 and
4 contain Broadband Group 2 primary interface modules, and slot 7 contains the
Broadband Group 2 backup module. The numbers on the cables correspond to
the steps in the Broadband Connection procedure on the previous page.
To power up, refer to
5
Connecting N+1 Protection Switch DC Power (-48VDC)
below.
Connecting N+1 Protection Switch DC Power (-48VDC)
To ensure DC power redundancy is maintained, use two DC Power Supply
Modules, in conjunction with power sources from two separate fuse panels or
from a fuse panel with redundant (A and B) fuse positions.