Specifications

ASMi-31 Ver. 3.0 Site Requirements and Prerequisites 2-1
Chapter 2
Installation and Setup
2.1 Introduction
This chapter describes installation and setup procedures for the standalone
ASMi-31 modem.
ASMi-31 is delivered completely assembled. It is designed for tabletop or 19-inch
rack installation. For rack installation instructions, refer to the rack mounting kit
for 19-inch racks guide that comes with the RM kit.
After installing the unit, refer to
Chapter 4
for configuration instructions. In case
a problem encountered, refer to
Chapter 5
for test and diagnostic instructions.
Internal settings, adjustment, maintenance, and repairs may be performed only
by a skilled technician who is aware of the hazards involved.
Always observe standard safety precautions during installation, operation, and
maintenance of this product.
Before installing the product, review
Handling Energized Products
at the
beginning of the manual.
2.2 Site Requirements and Prerequisites
ASMi-31 should be installed within 1.5m (5 ft) of an easily accessible grounded
AC outlet that furnishes 100 VAC to 240 VAC or a -48 or 24 VDC power source,
which must be adequately isolated from the mains supply.
Allow at least 90 cm (36 in) of frontal clearance for operating and maintenance
accessibility. Allow at least 10 cm (4 in) clearance at the rear of the unit for signal
lines and interface cables.
The ambient operating temperature of ASMi-31 is 0° to 50°C (32° to 122°F) at
relative humidity of 90%, non-condensing.