Owner`s manual

Analog Input Module
9-3
Figure 9-2 provides a detailed view of the AI module front panel.
ERR
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
24V
1
2
3
4
5
6
7
8
ERR
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
24V
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
OF
UF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
24V
8 AI Module 16 AI Module
Figure 9-2 ACE3600 I/O Module – Front Panel
AI Module Configuration
50/60 Hz Filtering
This parameter enables the user to configure the module to use 50 or 60 Hz filter on all inputs.
AI Filter (Smoothing)
This parameter enables the user to configure the level smoothing (averaging) on all inputs. It
can be set to 1, 2, 4, 8, 16, 32, 64,128 samples.
Change Of State (COS) Delta
This parameter sets a delta value to each input. This enables the user application program to
get an indication when the input value change is more than ± delta value.
Input Range
This parameter sets the overflow and underflow limits (refer to AI Module value representation
below.)