Owner`s manual
Power Supply Module and Backup Battery
3-4
Input/Output Connectors
The front panel of the power supply module includes the following connectors.
Connector Name Description Notes
Auxiliary Output 1A 13.2V DC (±20%)
User controlled power
output.
Short protected.
This output is used for
powering radios, modems,
etc.
The output can be switched
ON/OFF either by user
application program or by a
using the STS hardware test.
(Default = ON)
For more information, see the
Performing Hardware Tests
section or Application
Programmer section of
ACE3600 STS User Guide.
Auxiliary Output 1B Same as Auxiliary Output 1A Same as Auxiliary Output 1A
Auxiliary Output 2A DC Power Output
Selectable/programmable
3.3 to 9V DC or
13.2V DC±20%.
User controlled power
output.
Short protected.
This output is used for
powering radios, modems,
etc.
The output can be set by the
user with the STS
configuration function.
The output can be switched
ON/OFF either by a
hardware test or by user
application program. (Default
= OFF)
If both 2A and 2B are ON,
they must have the same
output level. The voltage
levels of AUX2A and
AUX2B are the same.
Auxiliary Output 2B Same as Auxiliary Output 2A Note: Auxiliary Output 2B
can be ON independently of
2A.
If both 2A and 2B are ON,
they must have the same
output level.
The voltage levels of
AUX2A and AUX2B are the
same.