Make sure that the ground wire on the user cable is long enough to reach the
grounding strip.
Connecting AC/DC Main Power
The power connection to all the ACE3600 power supply types is via the power junction box
located on the frame beneath the power supply slot.
Safety standards require that the power cable be attached to the unit at two anchor
points:
• Anchor point 1 for all units is inside the power junction box. (See Figure 2-12
below.)
• Anchor point 2 for the basic model (No I/O Slots Frame) is located on the right of
the power junction box. (See Figure 2-12 below.)
Anchor point 2 for all units with housing (other than No I/O Slots) is in the
housing power cable gland. (See Figure 2-16 below.)
Anchor point 2 for all other units without housing (other than No I/O Slots) is
near the unit’s ground strip. (See Figure 2-13 below.)
Clamp - Anchor Point
Clamp - Anchor Point
Figure 2-12. RTU on No I/O Frame – Cable Anchor Points 1 and 2