Appendix A: Specifications
A-2
Enclosures Large Nema 4X / IP65 painted metal
- up to 7 I/O slot frame, two radios
and 6.5 or 10 Ah, backup battery,
Dimensions (WxHxD): 500 x 500 x 210 mm (19.7" x19.7" x 8.26" )
Small Nema 4X / IP65 painted metal - up to 3 I/O slot frame one radio and
6.5 Ah backup battery,
Dimensions (WxHxD): 380 x380 x 210 mm (15" x 15" x 8.26")
Power Supply 10.5-16 V DC (default)
18-72 V DC
18-72 V DC with 12V smart battery charger
85- 264 V AC, 50-60 Hz
85- 264 V AC, 50-60 Hz, with 12V smart battery charger
Backup Battery 6.5 Ah - Sealed Lead-Acid
10 Ah - Sealed Lead-Acid
Operating Temperature -40 ºC to +70 ºC (-40 ºF to 158 ºF)
Storage Temperature -55 ºC to +85 ºC (-67 ºF to 185 ºF)
Operating Humidity 5% to 95% RH @ 50 ºC without condensation
Mechanical Vibrations Per EIA / TIA 603 Base-station, Sinusoidal 0.07mm @ 10 to 30 Hz, 0.0035
mm @ 30-60 Hz
Operating Altitude -400m to +4000 meter (-1312 ft to + 13120 ft) above sea level
Regulatory Standards
Safety UL 60950-1 (UL listed), CSA 22.2-950-1, EN60950-1, IEC 60950-1,
AS/NZS 60950
Emission Emission standards for industrial environments
CFR 47 FCC part 15, subpart B (class A);
CE EMC: EN50081-2/EN61000-6-4
(CISPER 11 / EN55011 class A)
Immunity Immunity standards for industrial environments
Per EN50082-2 /IEC 61000-6-2
Communications
Communication Ports Up to 5 Ports per CPU
Serial - up to 4 x RS232 ports
Multi-drop – up to 3 x RS485 port
Ethernet - up to 2 x 10/100 MB ports and 1 x 10 MB
Two-way radio / analog trunked radio - up 2 x modem ports