User guide
10
SOLA Never Stops Innovating
www.solaaust.com.au
Alarm Display
2 beeps per second.
Alarm Description
The UPS is overloaded (in Line
Mode). Your equipment needs more
power than the UPS can supply. The
UPS is operating in Bypass.
What You Should Do
Shut off the least important equipment
connected to the UPS. If this solves the
overload problem, the UPS will switch from
bypass back to normal operation.
2 beeps per second. The UPS is overloaded (in Battery
Mode). Your equipment needs more
power than the UPS can supply.
Shut off the least important equipment
connected to the UPS. Restart the unit by
turning it off and on again.
No beep. The UPS is performing a
battery test.
No action needed. The UPS returns to normal
operation when it successfully completes the
battery test.
Continuous beep. Battery test has determined the
batteries are overcharged.
Turn off protected loads. Turn off the UPS
and phone SOLA Service.
3 beeps every 5 seconds. Battery test has determined the
batteries should be replaced.
Phone SOLA Service.
Continuous beep.
Continuous beep.
2 beeps per second.
Continuous beep.
Continuous beep.
Short circuit in the inverter static
transfer switch.
Short circuit in the bypass static
transfer switch.
High internal DC bus voltage.
High output voltage or inverter short
circuit.
High internal temperature.
Phone SOLA Service.
Phone SOLA Service.
Phone SOLA Service.
Phone SOLA Service.
Make sure the unit’s fans and vent holes are
not blocked, and the ambient temperature is
not above 40 degrees C (104 ºF). If these
conditions do not exist, phone SOLA Service.
Table 1: Alarm Conditions
(A) (B) (C) (D) (E) (F)
(A) (B) (C) (D) (E)(F)
(A) (B) (C) (D) (E) (F)
(A) (B) (C) (D) (E) (F)
(A) (B) (C) (D) (E) (F)
(A) (B) (C) (D) (E) (F)
(A) (B) (C) (D) (E) (F)
(A) (B) (C) (D) (E)(F)
(A) (B) (C) (D) (E) (F)
(A) (B) (C) (D) (E)(F)










