User manual

PDU cascade port
ON
1
LINK OUT
RESET
ON DIP
1876
5
432
CURRENT
(
A
)
225
Current display
2
Dip switch
3
Reset button
4
ON DIP
1876
5
432
OFF
Using the dip switch no. 1, 2, 3, 4 & 8 to setup each PDU level acording to the table :
Cascaded PDUs Dip switch no.
12348
1st PDU On On On On Off
2nd PDU Off On On On Off
3rd PDU On Off On On Off
4th PDU Off Off On On Off
5th PDU On On Off On Off
6th PDU Off On Off On Off
7th PDU On Off Off On Off
8th PDU Off Off Off On Off
9th PDU On On On Off Off
10th PDU Off On On Off Off
11th PDU On Off On Off Off
12th PDU Off Off On Off Off
13th PDU On On Off Off Off
14th PDU Off On Off Off Off
15th PDU On Off Off Off Off
16th PDU Off Off Off Off Off
Cascaded PDUs setting
P. 1
For rackmount PDU, on the front panel left , on the rear panel
2 3 4 1
< 1.1 > PDU meter setting & cascade