Specifications

UPS BATTERY BACKUP CONFIGURATION LIST
append i x
PRO901L
PRO902L
PRO903L
PRO906L
PRO906LI
#1
2/24VDC
4/48VDC
6/72VDC
8/96VDC
8/96VDC
C1×1
12V40AH×2
C4×1
12V40AH×4
C3×1
12V40AH×6
C8×1
12V26AH×16
C8×1
12V26AH×16
C16×1
12V26AH×32
C16×1
12V26AH×32
C24×1
12V65AH×24
C24×1
12V65AH×24
C12×1
12V40AH×48
C12×1
12V40AH×48
C24×2
12V65AH×48
C24×2
12V65AH×48
C2×1
12V40AH×4
C4×1
12V40AH×8
C6×1
12V40AH×12
C4×1
12V65AH×4
C8×1
12V65AH×8
C6×1
12V100AH×6
C6×1
12V40AH×12
C12×1
12V40AH×24
C20×1
12V40AH×36
C8×1
12V65AH×8
C16×1
12V65AH×16
C20×1
12V100AH×18
1. ONLINE PROFESSIONAL SERIES (1P/1P) - TOWER
MODEL
30 Minutes
Quantity
DC
60 Minutes
Quantity
120 Minutes
Quantity
180 Minutes
Quantity
240 Minutes
Quantity
Remark
Battery
Group
1. Without cable from
UPS system to
battery bank.
2. All batteries supply
are without battery
cables.
2. ONLINE MASTER SERIES (1P/1P) - TOWER
MODEL
DC
Battery
Group
30 Minutes
Quantity
60 Minutes
Quantity
120 Minutes
Quantity
180 Minutes
Quantity
240 Minutes
Quantity
Remark
PRO801L
PRO815L
PRO802L
PRO803L
C1×1
12V26AH×3
C2×1
12V40AH×3
C3×1
12V26AH×6
C3×1
12V40AH×6
C3×1
12V26AH×6
C3×1
12V40AH×6
C6×1
12V26AH×12
C6×1
12V40AH×12
C2×1
12V38AH×3
C3×1
12V100AH×3
C6×1
12V65AH×6
C6×1
12V100AH×6
C12×1
12V26AH×18
C12×1
12V40AH×18
C20×1
12V26AH×36
C20×1
12V40AH×36
C3×1
12V38AH×6
C6×1
12V100AH×6
C12×1
12V65AH×12
C12×1
12V100AH×12
3/36VDC
3/36VDC
6/72VDC
6/72VDC
PRO806L
C12×1
12V26AH×20
C4×2
12V18AH×40
C20×1
12V26AH×40
C32×1
12V40AH×60
C20×2
12V65AH×40
20/240VDC
1. Without cable from
UPS system to
battery bank.
2. All batteries supply
are without battery
cables.
PRO806LI
#1
C12×1
12V26AH×20
C4×2
12V18AH×40
C20×1
12V26AH×40
C32×1
12V40AH×60
C20×2
12V65AH×40
20/240VDC
PRO806CL
C12×1
12V26AH×20
C4×2
12V18AH×40
C20×1
12V26AH×40
C32×1
12V40AH×60
C20×2
12V65AH×40
20/240VDC
PRO806CLI
#1
C12×1
12V26AH×20
C4×2
12V18AH×40
C20×1
12V26AH×40
C32×1
12V40AH×60
C20×2
12V65AH×40
20/240VDC
PRO810L
C12×1
12V40AH×20
C20×1
12V40AH×40
C20×2
12V65AH×40
C20×3
12V40AH×120
C20×2
12V100AH×40
20/240VDC
PRO810LI
#1
C12×1
12V40AH×20
C20×1
12V40AH×40
C20×2
12V65AH×40
C20×3
12V40AH×120
C20×2
12V100AH×40
20/240VDC
PRO810CL
C12×1
12V40AH×20
C20×1
12V40AH×40
C20×2
12V65AH×40
C20×3
12V40AH×120
C20×2
12V100AH×40
20/240VDC
PRO810CLI
#1
C12×1
12V40AH×20
C20×1
12V40AH×40
C20×2
12V65AH×40
C20×3
12V40AH×120
C20×2
12V100AH×40
20/240VDC
3. ONLINE MASTER SERIES (1P/1P) 2-IN-1 RACK/TOWER
MODEL
DC
Battery
Group
30 Minutes
Quantity
60 Minutes
Quantity
120 Minutes
Quantity
180 Minutes
Quantity
240 Minutes
Quantity
Remark
PRO801RL
PRO815RL
PRO802RL
PRO803RL
2/24VDC
3/36VDC
4/48VDC
6/72VDC
PRO806RL 20/240VDC
PRO810RL
C1×1
12V40AH×2
C3×1
12V65AH×3
C2×1
12V40AH×4
C3×1
12V40AH×6
C12×1
12V26AH×20
C12×1
12V40AH×20
20/240VDC
C2×1
12V40AH×4
C6×1
12V65AH×6
C4×1
12V40AH×8
C6×1
12V40AH×12
C20×1
12V26AH×40
C20×1
12V40AH×40
C3×1
12V100AH×2
C3×1
12V100AH×3
C4×1
12V100AH×4
C6×1
12V100AH×6
C20×1
12V65AH×20
C20×1
12V100AH×20
C6×1
12V40AH×12
C20×1
12V65AH×18
C12×1
12V40AH×8
C20×1
12V40AH×36
C32×1
12V26AH×120
C32×1
12V40AH×120
C4×1
12V100AH×4
C6×1
12V100AH×6
C8×1
12V100AH×8
C12×1
12V100AH×12
C20×2
12V65AH×40
C20×2
12V100AH×40
1. Without cable from
UPS system to
battery bank.
2. All batteries supply
are without battery
cables.
#1 Model with Isolation Transformer
All specifications, designs and contents are subjected to changes without prior notice.
38
Appendix