Specifications
Type
Charging Current
Configurable Battery
Full specifications
Power series (3p/3p) - PWR7000
PWR7020
MODELS
PWR7030 PWR7040 PWR7060
Type
BYPASS
Input Phase
Input Voltage Range
INPUT
20KVA
16KW
30KVA
24KW
40KVA
32KW
60KVA
48KW
3-Phase In / 3-Phase Out
Capacity
Phase
Isolation Transformer
Volt-Amp
Watt
NA
Total Harmonic Distortion (THDi)
Power Factor
< 3%
> 0.99
208~478 ±5VAC
46~54Hz ±0.5Hz or 56~64Hz ±0.5Hz
Voltage Range
Frequency Range
SYSTEM
Running Temperature
Relative Humidity
Remote Signaling
Communication Interface RS232 / RS485 / RJ11 / SNMP
0~40°C
Dry Contact
0%~95% (Non-Condensing)
Overload Capability
Frequency
Waveform
Linear Load
Non-Linear Load
OUTPUT
Voltage
Current Crest Ratio
Total Harmonic
Distortion (THD)
110%for 60mins
125%for 10mins
150%for 1min
3:1
< 1%
< 5%
380/400/415V
Sinewave
50/60Hz ±0.5Hz
Sealed lead acid maintenance free
15A Max.
32/34/36/38/40
Overload Capacity
Static bypass and manual maintenance bypass
3 phase 4 wire and ground
208~478V ±5V
< 125%keep normal
125%~170%for 10mins
Inverter Efficiency
Degree of Protection
Attitude
Noise at 1mm < 56dB
95%
1000m output nominal power
IP20
Gross Weight
PHYSICAL
Net Weight
Unit
Packaging
Dimension (mm)
D×W×H
Weight (kgs)
230
210
235
215
696×603×1194
830×703×1380
245
225
290
270
696×603×1796
830×703×1980
• Advanced IGBT rectifier with low THDi and high PF
• Wide input voltage range and frequency tolerance
• Load bus synchronization (LBS) function
• Flexibility of configurable battery quantity
• Front accessible module design for ease of maintenance
• Low audible noise and low output voltage THD
• Parallel redundancy
• ECO mode
• Back-feed protection
• Cold start
• LCD and LED user interface with audible alarm function
• Surge, short circuit and overload protection
BATTERY