Specifications

Power Series (3p/3P)
• Online double conversion technology with DSP control
• Advanced control with Adaptive Feed Forward Cancellation (AFC) technology
for very low harmonic distortion
• Very low input current distortion (THDi < 1%)
• Input power factor 0.99 at 10%load
• Output efficiency up to 95%
• Space-saving compact design
• Front access makes maintenance and replacement easily
• Highly flexibility in single phase / three-phase set-ups
• Control designed to withstand all kinds of loads
• Variety of communication options available
• Over 60%materials recyclable
• Optional N+X parallel redundancy
• Remaining backup time calculation
If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
Indications of Models: L means Long-run model; S means Standard model; I means Isolation Transformer available (optional).
All specifications, designs and contents are subjected to changes without prior notice.
OnlinE UPS
18
Online
Full specifications
15KVA
12KW
20KVA
16KW
30KVA
24KW
40KVA
32KW
60KVA
48KW
80KVA
64KW
PRO73315 (S/SI)MODELS PRO73320 (S/SI) PRO73330 (S/SI) PRO73340 (S/SI) PRO73360 (S/SI) PRO73380 (S/SI)
Volt-Amp
Watt
Capacity
Humidity
Protection
Regulations
ENVIRONMENT
Type
Voltage
Frequency
Overall Efficiency (Line Mode)
MANUAL BYPASS (MAINTENANCE)
Without Interruption
3×400V (3Ph + N)
50/60Hz
92.0%91.0%90.5% 92.5% 93.05% 94.0%
Type
STATIC BYPASS
Voltage
Current Limit
Admissible Crest Factor
Admissible Power Factor
Admissible Overload
Imbalance Output Voltage @ 100%Unbalanced Load
Dynamic Recovery Time
INPUT
Phase
Output Power Factor
Isolation Transformer
3 Phase In / 3 Phase Out
0.8
Optional
Nominal Voltage
Frequency
Activation Criterion
Transfer Time
Solid State
3×400V (3Ph + N)
50/60Hz
Microprocessor Control
Zero
400%for 10sec.
Immediate, for overload above 150%
Automatic after alarm clear
Admissible Overload
Transfer to Bypass
Retransfer
Acceptable Voltage Range
Frequency
Total Harmonic Distortion (THDi)
3×400V (3Ph + N)
+15% or -20%
50/60Hz ±5%
<1.0%@ 100% Load
<2.0%@ 50% Load
<5.0%@ 10% Load
<1.5%@ 100% Load
<2.5%@ 50% Load
<6.0%@ 10% Load
High Overload: PFC Limit (discharging batteries)
1.0
Current Limitation
Power Factor
Non-Linear Load
Precision
Frequency
Phase Displacement
Waveform
Total Harmonic
Distortion (THDv)
Linear Load
Imbalanced Load 50%
Balanced Load
INVERTER
Nominal Voltage
Maximum Synchronisation Speed
Pure Sinewave
< 0.5%
50/60Hz Synchronised ±4%
3×400V (3Ph + N)
Stationary: ±1% Transitory: ±2% (Load Variations 100%-0%-100%)
±1Hz/s
< 1.5%
< 1%
3.4:1 3.2:1
10ms. @ 98%of the static value
125%for 10min., 150%for 60sec.
0.1 inductive to 0.1 capacitive
120° ±1%
120° ±2%
High Overload, Short-circuit: RMS Voltage Limit
IP20
0-95% Relative Humidity @ 0-40°C (Non-Condensing)
EN 62040-2:2006, EN 61000-2-2:2002, EN61000-4-2,3,4,5,6,8
Dimension (mm) D×W×H
Net Weight (Without Batteries) (kgs)
Build-in Batteries Type (2×31)
Net Weight (With Built-in Batteries) (kgs)
PHYSICAL
190 200 300120
980×650×1320
700×450×1100
530250250 NA NA
12V 12AH12V 7.2AH12V 7AH 12V 18AH NA NA