Specifications

MASTER serieS (1p/1p) - Tower
OnlinE UPS
8
Online
Output power factor 0.8
Compared to the online UPSs in the current market, Master
Series (1P/1P) provides better output power factor up to 0.8.
It offers higher performance and efficiency for critical
applications.
Wide input voltage range (110 V -300 V)
Master Series (1P/1P) can still provide stable power to
connected devices under unstable power environments.
50/60 Hz Frequency Converter Mode
Lock output frequency at 50Hz or 60Hz to suit power
sensitive equipments.
ECO mode operaon for energy saving
Offers efficiency as high as 97% to cut energy usage & cost.
UPS power application via static bypass, timely returning to
online double conversion when the need arises.
SNMP+USB+RS-232 mulple communicaons for
1-3K models
This feature allows either USB or RS-232 communication
port to work with SNMP interface simultaneously.
Emergency Power Off (EPO) Funcon
This feature can secure the personnel and equipment in case
of fires or other emergencies.
True double-conversion online UPS
A true double conversion UPS will provide clean, high level
quality power to fully protect mission-critical devices such as
sensitive networks, small computer centers, servers, telecom
applications, as well as for industrial applications.
Smart baery charger design to opmize baery
performance
• Master Series (1P/1P) 1-3K is equipped with 2-stage
charger design to guarantee battery discharge time.
Besides, it will adjust charging voltage according to
outside temperature. This features will extend the useful
service life of batteries.
• Master Series (1P/1P) 6K and up models are equipped with
3-stage extendable charger for optimized battery
performance. This feature extends the useful service life of
batteries and optimizes battery recharge time. Besides, the
extendable charger design can be stacked in numbers for
large-capacity battery charging.
DSP technology applied for 6K and up models
A DSP controller provides an improved and cost-effective
solution with high performance.
Maintenance bypass available for 6K and up models
Internal bypass assures continuous power to critical devices
during UPS maintenance.
Oponal hot standby mode and N+X parallel
redundancy available for 6K and up models
For genuinely redundant power protection, Master Series
(1P/1P) (6K and up models) can either be used in parallel
operation with up to 3 units or hot standby mode. Slave UPS
will back up the load in the event of critical component
failure. It increases power safety and availability.
Built-in isolaon transformer (Opon)
With built-in isolation transformer, the UPS will offer full
isolation and complete common mode noise rejection for
connected precious equipment. It become an ideal power
source with 100% protection against unexpected AC power
problems.
Adjustable baery numbers for 6K and up models
Master Series (1P/1P) (6K and up models) can still normal
operate well with only 18 or 19 internal batteries.
Higher accuracy for output voltage
With advanced control firmware, Master Series (1P/1P)
provides high accuracy within +/- 1% for output voltage. It
can be applied to precious test & IT equipment.
Programmable power management outlets
With programmable power management
outlets, users can easily and independently
control load segments. During power failure,
this feature enables users to extend battery
time to missioncritical devices by shutting
down the non-critical devices.
Programmable Outlets (P1)
- connect to non-critical devices
All specifications, designs and contents are subjected to changes without prior notice.