14.1.10 Fault Supply vol F_SPh
Main supply fault, one phase missing
Check that the main voltage connects simultaneous to the control voltage
Check the connections of the terminals 19 (U1-1), 17 (U1-2) and 15 (U1-3)
In insulated or high impedance grounded networks, the zero level floats, causing errors in detecting
the actual supply voltage. Set parameter 4-10-3 to NO
14.1.11 Fault Phaseorder F_Sor
Main supply fault, incorrect phase order (supervision is carried out only once after each power-
ON)
Check the connections of the terminals 19 (U1-1), 17 (U1-2) and 15 (U1-3)
Check the phase-order
Check the phase order of the wires through the current transformers
Check the connections of the current transformer
In insulated or high impedance grounded networks, the zero level floats, causing errors in detecting
the actual supply voltage. Set parameter 4-10-3 to NO
14.1.12 Fault CParameter F_CP
Internal parameter read or write fault
Incorrect check sum in reading the memory or internal hardware fault in the unit
14.1.13 Fault MParameter F_MP
Internal parameter read or write fault
Incorrect check sum in reading the memory or internal hardware fault in the unit