Owner`s manual
3
NO. L-F2-09009
REV 8 - 0911111305
G18 SPECIFICATIONS AND REQUIREMENTS
The minimum size of fi replace for installation of Real-Fyre
®
G18 unvented gas log set: (refer to Fig. 3-1)
Burner Model
Log Set
Fireplace Size
BTU Input Rating
Size
Width Depth Height
Natural Gas Propane Gas
G18-24/30(P)
G18-24/30-15(M)(P)
G18-24/30-12(M)(P)
G18-24/30-01V(P)
24"
30" front
20" rear (min.)
14" (min.) 18" 38k 36k
30"
36" front
26" rear (min.)
14" (min.) 18" 38k 36k
APPROVED INSTALLATIONS
Subject to minimum fi replace size requirements
specifi ed below:
1. Solid-fuel-burning fi replaces;
A) Prefabricated fi replaces listed to UL-127
B) All other masonry fi replaces
2. Universal-listed vent-free fi replaces.
Note: Installation in any other fi replace is prohibited
and will void any approvals and warranties.
Fireplace Dimensions
Fig. 3-1
The G18 series vent-free gas log sets are available with
a variable fl ame height control valve that can be used
with a remote transmitter and receiver (not included
with models numbers ending in M or MP).
A spark ignition system (piezo) allows the gas pilot to be
lit without the use of matches, and permits the operation
of the appliance during a power outage.
This vent-free gas log set is equipped with an Oxygen
Depletion Sensor (ODS) safety pilot system. The ODS
senses the amount of oxygen available in the room
and shuts the log set off before the oxygen level drops
below 18%. The pilot can only be relit when fresh air
is available. This may require opening a window or
a door to another room or cracking the damper
open slightly.
This gas log set has been certifi ed to two standards:
UNVENTED ROOM HEATER-ANSI Z21.11.2.2-2007
VENTED DECORATIVE APPLIANCE-ANSI Z21.60b-2004
Check local or state codes to determine if vent-free
heaters are permitted in your locality before you install
this log set as a vent-free appliance. If not permitted,
you may install and operate this log set as a vented
appliance.
Important: For safe operation and proper performance of this product and to comply with certifi cation,
listings, and building code acceptances, use ONLY Peterson Real-Fyre
®
controls, parts, and
accessories that have been specifi cally listed or certifi ed for use with this burner system. Use
of other controls, parts, or accessories is prohibited and will void all warranties, certifi cations,
listings, and building code approvals, and may cause property damage, personal injury, and
loss of life.
This unit may not be installed in a vented fi replace with
a chimney of less than 15 feet in height.
Observing minimum fireplace dimensions and
centering the appliance in the fi replace will assure
adequate clearance for operation and servicing. It may
be necessary to uninstall the unit for some types of
service.
DEPTH
HEIGHT
FR ONT
WIDTH OPENING
Rear
width
Height
Front
width opening
Depth
Minimum Permanent Chimney Vent
Opening
Table 3-1 Factory built
fi replaces
Masonry built
fi replaces
Chimney Height 24/30 models 24/30 models
15' 22.53 sq. in. 26.53 sq. in.
20' 20.24 sq. in. 24.24 sq. in.
25' 19.20 sq. in. -
30' 18.09 sq. in. 22.09 sq. in.
35' 16.00 sq. in. -
40' 15.00 sq. in. -