Owner`s manual
15
IMPORTANT
CHECK GAS TYPE (natural or propane). The gas supply must be the same as stated on the gas log set
rating plate. If the gas supply is different,
DO NOT INSTALL. Contact the dealer for immediate assistance.
Note: To install the Real-Fyre
®
vent-free gas log set, the fi replace must have a gas supply line that has
been installed by a qualifi ed professional technician in accordance with all local codes.
Important: Be sure you have read and understand all safety precautions and warnings contained in
this manual.
Tools Required:
1. Adjustable open-ended wrench
2. Pliers
3. Propane gas resistant pipe compound or Tefl on
tape
BE SURE THE GAS SUPPLY TO THE FIREPLACE IS TURNED OFF.
BEFORE PROCEEDING, CAREFULLY READ ALL OF THE IMPORTANT SAFETY INFORMATION
CONTAINED IN THIS OWNER’S MANUAL, INCLUDING:
A. PRE-INSTALLATION AND FIREPLACE PREPARATION SAFETY GUIDELINES.
B. VENTILATION AND CONFINED SPACE SAFETY INFORMATION.
C. INSTALLATION SAFETY GUIDELINES.
CONNECTING THE GAS TO THE BURNER SYSTEM
This appliance is for installation in a solid fuel burning fi replace (masonry fi replace or manufactured fi replace)
with a working fl ue and constructed of noncombustible material.
These gas logs may be installed as vented decorative log sets in compliance with ANSI Z21.60b-2004 and
National Fuel Gas Code, Section 6.6. The minimum permanent free opening of the fi replace chimney or
chimney damper must be at least 14.1 sq. in. based upon a minimum chimney height of at least 15'. The
chimney damper must be fi xed in a manner to maintain a permanent opening free of obstruction at all times.
To accomplish this, you may install a screw or bolt in the edge of the damper to prevent closing, drill holes in
the damper, or remove the damper.
4. Soapy water solution & brush for leak detection
5. Flat-head screwdriver
6. Manometer (recommended for checking gas
pressure)
WHEN USED AS A VENTED DECORATIVE APPLIANCE (PER ANSI.60b-2004)
Refer to the PARTS LIST when installing the vent-free gas log set.