Owner`s manual

4
L-A2-250
REV 3 - 1305230925
Keep the area of the gas burner system clear and
free from combustible materials, gasoline, and other
ammable vapors and liquids.
The Real-Fyre
®
gas burner system is to be installed
only in a fully vented, noncombustible fi replace with
an open damper. The chimney must be free of any
obstructions. The fi replace must be designed and
approved to burn wood.
The fi replace must have a gas supply line that has
been installed by a qualifi ed technician in accordance
with all local codes.
Be sure to clean the fi replace fl oor of any ashes or
other foreign materials. It is recommended that the
replace and chimney be inspected by a chimney
sweep or other qualifi ed person before you install the
Real-Fyre
®
gas burner system.
Required Gas Pressure: The minimum inlet gas
supply pressure for the purpose of input adjustment
is 5" water column (w.c.) for natural gas and 11"
w.c. for propane gas. The maximum inlet gas supply
pressure is 10.5" w.c. for natural gas and 13" w.c. for
propane gas.
FIREPLACE SIZE REQUIREMENTS
Testing the Gas Supply System: The gas burner
system and its individual shut-off valve must be
disconnected from the gas supply piping system
while performing any tests of the piping system at
pressures in excess of
1
/
2
psig. The gas burner system
must be isolated from the gas supply piping system
by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system
at test pressures equal to or less than
1
/
2
psig. This
is accomplished by closing the gas supply line valve.
A fi replace screen must be in place when the
system is burning. Provisions for adequate
combustion air must be maintained. Unless other
provisions for combustion air are provided, the screen
shall have an opening(s) for introduction of combustion
air. Combustion air is adequate when all fl ames curl
into the fi replace and away from the screen. When a
glass fi replace enclosure (door) is used, leave the
doors fully open when the system is in operation.
GENERAL INFORMATION
Note: The minimum chimney height from hearth to top of chimney is 15'.
* This required width allows for centering of the system.
Burner
size
Min. Fireplace Dimensions
BTU
Width* Depth Height
NAT. L.P.
16/19" 26" 14" 18" 45k 30k
18" 28" 14" 18' 75k 55k
24" 34" 14" 18" 85k 65k
30" 40" 14" 18" 95k 70k
36" 46" 14" 18" 100k 70k
Minimum Free Opening Area of Chimney Damper for Venting (sq. in.)
For Factory-Built Fireplaces For Masonry-Built Fireplaces
Chimney
16/19" 18"
24"
30" 36" 16/19" 18"
24"
30" 36"
15' (min.) 20 36 42 47 47 30 46 52 57 60
20' 17 29 35 41 43 27 43 47 52 54
25' 1526303437-----
30' 13 23 27 31 34 25 39 43 47 49