Owner`s manual

11
REV 4 - 0705040838
No.L-A2-21507
IMPORTANT INFORMATION
Do not use this log set if any part has been underwater.
Immediately call a qualified professional service
technician to inspect the appliance and to replace
any part of the control system and any gas control
that has been underwater.
The appliance and its individual shutoff valve must
be disconnected from the gas-supply piping system
when testing the system at test pressures in excess
of ½ psig. This is accomplished by closing the gas-
supply line valve.
Keep the area of the gas log set clear and free from
combustible materials, gasoline, and other fl ammable
vapors and liquids.
The minimum inlet gas-supply pressure for the
purpose of input adjustment is 5" for natural gas
and 11" for propane gas. The maximum inlet gas-
supply pressure for this burner is 14" for natural
and propane gas.
A fi replace screen must be in place when the log
set is burning. Provisions for adequate combustion
air must be maintained. Unless other provisions for
combustion air are provided, the screen shall have
an opening(s) for introduction of combustion air.
Combustion air is adequate when all fl ames curl into
the fi replace and away from the screen.
When glass fi replace doors are used, operate the
gas log set with the doors open.
The minimum-size fi replace in which the log set is to
be installed is listed in the technical data table below.
The minimum chimney height from the hearth to the
top of the chimney is 15'.
.
THIS GAS LOG SET CONFORMS TO THE
ANSI Z21.60b -2004 STANDARD.
Note: A damper stop clamp is provided as a means to prevent full closure of the damper blade. Fully
open the damper when burning the log set (see the next page for details on the damper clamp).
The log set is designed to burn with yellow fl ames; adequate ventilation is absolutely necessary.
The chimney damper must be fi xed in a manner to maintain the permanent free opening at all times. To
accomplish this, you may install a screw or bolt in the edge of the damper to prevent closing, drill holes in the
damper, or remove the damper.
Important: To comply with certifi cation, listings, and building code acceptances, and for safe operation
and proper performance of this log set, use ONLY Peterson Real-Fyre
®
parts and accessories.
Use of other controls, parts, and accessories that are not designed for use with Real-Fyre
®
gas log sets is prohibited and will void all warranties, certifi cations, listings, and building code
approvals, and may cause property damage, personal injury, or loss of life.
Log set
size
Minimum fi rebox dimensions BTU Rating
Front
opening
Depth Height Natural Propane
18" 24" 13" 20" 40,000 40,000
20" 26" 13" 20" 40,000 40,000
24" 30" 13" 20" 55,000 55,000
30" 36" 13" 20" 65,000 65,000
Minimum permanent free opening area of chimney damper for venting
For factory-built fi replaces
log set sizes
For masonry-built fi replaces
log set sizes
Chimney
height
18" 20" 24" 30" 18" 20" 24" 30"
15' 15 sq. in. 15 sq. in. 21 sq. in. 29 sq. in. 23 sq. in. 23 sq. in. 31 sq. in. 40 sq. in.
20' 14 sq. in. 14 sq. in. 18 sq. in. 24 sq. in. 21 sq. in. 21 sq. in. 28 sq. in. 36 sq. in.
30' 10 sq. in. 10 sq. in. 15 sq. in. 19 sq. in. 19 sq. in. 19 sq. in. 26 sq. in. 33 sq. in.