Owner`s manual

13
INSTALLATION
Fig. 13-1 Damper clamp in place
1. Locate the gas-supply line valve. The
gas supply-valve must be OFF before
beginning the installation.
2. A damper clamp (PARTS LIST, Item #3) is
supplied and must be installed on the damper assembly as
shown in Fig. 13-1.
a. Open the fi replace damper.
b. Attach the damper clamp on the damper blade and
secure with the bolt.
Note: The damper clamp must be permanently installed.
Should the clamp not fi t, install a permanent
damper stop or other means of preventing full or
accidental closure such as removing the damper
blade.
Important: When the glass burner is operating, the damper
must be fully open.
WARNING
Failure to position the parts in accordance with these
instructions and diagrams, or failure to use only parts
specifi cally approved with this appliance, can result in
property damage or personal injury.
3. Clean the fi replace fl oor of any ashes.
4. Locate the gas-supply stub inside the fi replace and
remove the cap, if attached (see Fig. 13-2).
CAUTION: When removing the cap, make sure the stub
does not turn. It will loosen the connection
inside the wall.
Note: The gas-supply pipe must be ½" minimum inside
diameter (I.D.) or larger (¾" if gas line is longer than
20').
5. Attach the NPT side of the connector kit fi tting to the
replace gas stub (see Fig. 13-3), using Tefl on tape
or pipe compound resistant to propane gasses on the
stub. Tighten securely.
6. Attach the fl exible connector to the fl are side of the
connector kit fi tting to the fuel injector or air mixer
on burner pan (see Fig. 13-4) using Tefl on tape or
pipe compound resistant to propane gasses. Tighten
securely.
Open Closed
TO INSTALL THE GLASS BURNER, THE FOLLOWING
STEPS BELOW MUST BE FOLLOWED.
OFF
Use second
wrench to
stop pipe
from turning
Use wrench
to remove
stub cap
Fig. 13-2 Removing the stub cap
Attach fi tting to stub
Fig. 13-3 Attaching the elbow
Attach fl ex connector to fi tting
Fig. 13-4 Adapter on pan
This glass burner must be installed by an NFI Certifi ed or other qualifi ed installer. The installation,
including provisions for combustion and ventilation air, must conform with local codes, or, in the absence of
local codes, with the latest edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54).