Log sets are designed for use with natural gas, unless clearly labeled for propane gas. Never use propane gas
in a log set designed for natural gas, or natural gas in a log set designed for use with propane gas.
The installation, including provisions for combustion and ventilation air, must conform with local codes, or in the
absence of local codes, with the National Fuel Gas Code, ANSI Z223. 1 and NFPA54.
The appliance and its individual shutoff valve must be disconnected from the gas-supply piping system when
testing the system at test pressures in excess of ½ psig. This is accomplished by closing the gas-supply line
valve, as required by NFPA54.
The appliance must be isolated from the gas-supply piping system by closing its individual manual shutoff valve
during any pressure testing of the gas-supply system at test pressures equal to or less than ½ psig.
The minimum inlet gas-supply pressure for the purpose of input adjustment is 7" water column (w.c.) for natural
gas and 11" w.c. for propane gas.
The maximum inlet gas-supply pressure for this burner is 10½" w.c. for natural gas and 13" w.c. for propane
gas.
A fi replace screen must be in place when the log set is burning.
CAUTION: Where fi tted, operate the log set with the fi replace doors fully open.
The recommended fi rebox dimensions in which the G4-2 burner is to be installed are listed in the table below:
IMPORTANT INFORMATION
CHECK THAT THE LOG SET IS LABELED FOR THE PROPER GAS TYPE
TABLE OF CONTENTS
IMPORTANT INFORMATION 2
PARTS LIST 3
HOW TO INSTALL THE G4 SEE-THRU GAS LOG SET 4
BURNER CONNECTION INSTALLATION 4
BURNER PLACEMENT 4
CONNECTING THE GAS SUPPLY 4
HOW TO INSTALL THE REAL-FYRE
®
GAS LOG SET 5
GRANULE PLACEMENT 5
GLOWING EMBER & GRATE PLACEMENT 5
LOG PLACEMENT 5
DAMPER CLAMP 5
LOG PLACEMENT SUGGESTIONS 6
LIGHTING INSTRUCTIONS 8
MAINTENANCE AND SERVICE 9
MAINTENANCE 9
SERVICE 9
FLAME DESCRIPTION 9
TROUBLESHOOTING THE GAS LOG SET 9
OPTIONAL CONTROLS FOR YOUR REAL-FYRE
®
BURNER SYSTEM 11
WARRANTY 12
Note: Bracketed log sets exceed the
90,000-BTU maximum input allowed
by the LA Standard and are not
included in the RADCO listing.
Log
Set
Size
Minimum Fireplace Dimensions
BTU
(natural)
BTU
(propane)
Depth Height
Width
†
Min. vent
opening
sq. in. *
12"
15" 18"
18" 25 40k 30k
16/19"
16" 18"
25" 29 50k 45k
18/20"
18" 18"
26" 51 75k 50k
24"
18" 18"
30" 57 90k 65k
30"
18" 18"
36" 57 90k 65k
[36"]
20" 18"
42" 82 130k 100k
[42"]
20" 18"
48" 94 150k 120k
[48"]
20" 18"
54" 107 170k 130k
[60"]
20" 18"
66" 120 190k 140k
Front
Rear
Opening
width
Depth
Front width
height
Fig. 2-1 Fireplace dimensions
Note: Front and rear width are assumed the same
for see-through fi replaces.
* The chimney vent opening provided is based
upon a required minimum chimney height
of 15 feet.
† This required width allows for centering of
the log set. Add 4" to front width if the burner
is to be installed with a pilot kit.