MINIMUM CLEARANCES TO COMBUSTIBLES
If the vent-free burner system is installed in a factory
built fi replace, follow the manufacturer’s guidelines for
minimum clearances to combustibles.
In the absence of such guidelines, follow the instructions
below:
Clearances to Combustible Construction:
Sidewalls
: 16" from side of fi replace opening (Fig. 6-1).
Ceiling: 42" from top of fi replace opening (Fig. 6-1).
Flooring: See IN FRONT OF FIREPLACE section below.
Mantel: See ABOVE THE FIREPLACE section below &
Fig. 6-1. Also see Fig. x-1, & x-2 on following page).
Note: Clearances to combustible construction
are those distances required to ensure that
replace mantels, facings, walls, ceilings, and
oorings will not catch fi re.
In most cases, these clearances should also be
adequate to prevent any discoloration or warping due
to heat. However, every gas burner installation presents
a different and unique set of circumstances involving
many variables beyond the control of the manufacturer.
These include paint or fi nish composition, previous
exposure to heat, methods and quality of construction,
air fl ow patterns, glass doors, fans or blowers, etc.
Because of these variables, we cannot guarantee that
heat warping or discoloration will never occur. The
potential for heat warping or discoloration may exist
no matter what item(s) you are burning in the fi replace,
including wood.
The dimensions in Fig. 6-1 are MINIMUM
CLEARANCES to maintain when you install this
burner system. BOTH SIDES of the fi replace opening
MUST BE AT LEAST 16" from any combustible
sidewalls. The ceiling MUST BE at least 42" from
the top of the fi replace opening.
ABOVE THE FIREPLACE:
To install the vent-free burner system, there must ALWAYS be noncombustible or heat resistant material
immediately above the fi replace opening. Heat resistant materials (i.e., marble or slate) must be at least
5
/
8
"
thick. Sheet metal should not be installed onto combustible materials.
If you DO NOT install a fi replace hood, there MUST be at least 12" of noncombustible or heat resistant material
immediately above the fi replace opening (see A in Fig. x-1 on the following page). If you DO install a fi replace
hood, there MUST be at least 10" of noncombustible or heat resistant material immediately above the fi replace
opening (see B in Fig. x-2 on the following page). If there is a wooden mantel, shelf, or other combustible
projection above the fi replace, follow the information in the Figures on the next page.
EXAMPLE: If the fi replace has a combustible projection (mantel or shelf) 20" above the top of the fi rebox,
the maximum horizontal projection out from the face of the fi replace will be:
1. If a fi replace hood is not installed - 2.5" (see Fig. x-1 on the following page).
2. If a fi replace hood is installed ------ 10" (see Fig. x-2 on the following page).
A fi replace hood defl ects heat away from the fi replace face and mantel, reducing the potential for heat related
warping or discoloration. The use of a fi replace hood is highly recommended.
IF YOU CANNOT MEET THESE MINIMUM CLEARANCES, YOU MUST OPERATE THE VENT-FREE
BURNER SYSTEM WITH THE CHIMNEY FLUE DAMPER OPEN.
IN FRONT OF THE FIREPLACE:
Be certain that combustible fl ooring material (i.e.: carpet, tile, etc.) is not too close to the vent-free unit. If the
vent-free burner system is at fl oor level or less than 6" above the fl oor, there MUST be at least 12" (1 foot) of
noncombustible material between the front of the fi replace and any combustible fl ooring.
42"
16"
Fig. 6-1
Minimum clearances to
side walls and ceiling
Side wall: 16" from side of fi replace opening.
Ceiling: 42" from top of fi replace opening.