Owner`s manual

21
OPERATING THE LOG SET - LIGHTING AND EXTINGUISHING
After setting the logs into position as described on the previous page, ensure each is properly and fi rmly seated.
The vent-free gas log set will not function as intended if the logs are not correctly positioned. When placed
properly, the fl ames will not strike any portion of the top logs. Periodically check the positioning of all logs to
ensure proper log placement and stability. If any fl ame is striking the top logs, recheck log placement. Adjust
to conform with these instructions. There should be no fl ame impingement on these logs.
INSTALLATION (Cont.)
Note: We recommend that before you install the log set, you familiarize yourself with the control valve layout.
This will help you to be confi dent operating the log set when fully installed.
IMPORTANT
For all valves, the air MUST be purged from the gas line before the ODS pilot will light properly. The time taken
to do this will depend on the length of gas line from the meter to the unit and the length of time since the unit
or gas line was last used (in the case of non-use during warm weather, for example). It may take from 3-15
minutes before all the air is purged and the ODS pilot will light properly. This is done using the method for lighting
the ODS pilot, but holding in the control valve for a longer period. Follow the LIGHTING INSTRUCTIONS in
this manual for the specifi c valve type.
CAUTION: BURN HAZARD. Logs will remain hot for some time after use. You must maintain the
log layout as shown to ensure proper operation of the log set. If you need to reposition
any log to maintain the proper layout, use heat-resistant gloves or allow logs adequate
time to cool before handling.
DAMPER CLAMP INSTRUCTIONS
The damper clamp with hex bolt (Fig. 21-1) is provided as a means to prevent full closure of the damper blade.
The clamp is easily attached to most damper blades with pliers or a wrench, and must be permanently installed.
The clamp is designed to prevent accidental closure of the damper when installed as illustrated (Fig. 21-2
and Fig. 21-3). Should the clamp not fi t, or fail to provide the permanent vent opening specifi ed in Table 3-1,
have a permanent stop installed, remove the damper blade, or have the damper cut to provide the minimum
permanent opening required.
Damper clamp
Fig. 21-1
Set screw
Fig. 21-2 Fig. 21-3
Open
Closed