Owner`s manual

4
L-A2-159
REV 6 - 1301300913
DO NOT USE the gas log set if any part has been
underwater. Immediately call a qualified service
technician to inspect the gas log set and to replace
any part of the control system and any gas control
which has been underwater.
Peterson Real-Fyre
®
gas logs must be installed only
in a wood burning fi replace with the minimum venting
requirements met (see table on this page). Gas supply
pipe must be
1
/
2
" minimum interior diameter. If the gas
line is longer than 20', a larger diameter line may be
necessary.
DO NOT INSTALL the log set where completely
sealed doors are used. Doors must have a combined
air gap opening of no less than 18 square inches.
A fi replace screen must be in place when the system
is burning. Provisions for adequate combustion air
must be maintained. Unless other provisions for
combustion air are provided, the screen shall have
an opening(s) for introduction of combustion air.
Combustion air is adequate when all fl ames curl into
the fi replace and away from the screen.
The gas log set must be isolated from the gas supply
piping system by closing its individual shut-off valve
during any pressure testing of the gas supply system
at test pressures equal to or less than
1
/
2
psig. The
gas log set and its individual shut-off valve must be
disconnected from the gas supply piping system when
testing at pressures in excess of
1
/
2
psig.
Keep the area of the gas log set clear and free from
combustible materials, gasoline, and other fl ammable
vapors and liquids.
The minimum inlet gas supply pressure for purpose
of input adjustment is 5" for natural gas and 11" for
propane gas. Maximum inlet gas supply pressure for
this burner is 10.5" for natural and 13" propane gas.
The minimum fi rebox dimensions in which the log set
is certifi ed to be installed, are listed in the table below.
Maintenance and service must be performed by the
gas supplier, or other qualifi ed professional.
Burner
Model
Minimum Fireplace Size BTU Rating
Width Depth Height
Natural Gas Propane Gas
GF-16/18-11(P) 20" 15" 17" 35k 31k
GF-24-11(P) 27" 15" 17" 45k 41k
GF-30-11(P) 32" 15" 17" 55k 51k
GENERAL INFORMATION AND SPECIFICATIONS
DAMPER CLAMP INSTRUCTIONS
The damper clamp with hex bolt (Fig. 4-1) is provided as a means to prevent
full closure of the damper blade. The clamp is easily attached to most
damper blades with pliers or a wrench, and must be permanently installed.
The clamp is designed to prevent accidental closure of the damper when
installed as illustrated (Fig. 4-2 and Fig. 4-3). Should the clamp not fi t, or
f
ail to provide the permanent vent opening listed in the table found above,
have a permanent stop installed, remove the
damper blade, or have the damper cut to provide
the minimum permanent opening required.
Note: These are minimum damper opening
specifications. The damper must be
completely opened when operating
this gas appliance to achieve the best
ventilation possible.
Fig. 4-1
Damper clamp
Set screw
Note: The minimum chimney height from hearth to top of chimney is 15'.
Minimum permanent free opening area of chimney damper for venting
For factory-built fi replaces For masonry-built fi replaces
Chimney
height
16/18" 24" 30" 16/18" 24" 30"
15' 22 sq. in. 28 sq. in. 34 sq. in. 26 sq. in. 32 sq. in. 38 sq. in.
20' 20 sq. in. 25 sq. in. 31 sq. in. 24 sq. in. 29 sq. in. 35 sq. in.
30' 18 sq. in. 23 sq. in. 28 sq. in. 22 sq. in. 27 sq. in. 32 sq. in.
Fig. 4-2 Fig. 4-3
Open
Closed