CHAPTER 1 Installing Hardware Components
Page 24 of 64 Quick Response Premiere Wireless Call System Hardware Installation Guide
0510-1099-E
The Configuration Rooms Properties window opens.
a. Name—enter the 32 Channel Controller name.
b. Supervised—select this check box if you wish to have the device supervised.
c. Supervised Time—select the amount of time, from the drop-down list, that the
system should wait before it initiates a Device Fault alarm. The Unit Default time is
the Transmitter Supervise Time set during Unit Properties configuration.
d. Type—the type of device is provided for you.
e. Channel—choose the channel assigned to the Gateway/Router (default 25). Channel
selection is site specific and dependent on the sites environmental issues.
f. Router/Relay Association—select the devices associated with a relay. There are 32
relays; each relay is capable of monitoring four devices. The Dome Light is triggered
if any of the devices associated with that relay goes in alarm. Devices selected must
be from the same unit as the 32 Channel Controller.
g. Click Save to save your changes
h. Click Close to close the window without saving your changes.